355 IAC 3-2-9
355 IAC 3-2-9 Filling densities
Cite as Ind. Admin. Code tit. 355, r. 3-2-9
Sec. 9. (a) The filling densities for nonrefrigerated containers shall not exceed the following:
Aboveground
(1) Uninsulated 56%*
(2) Insulated 57%
(3) DOT containers shall be filled in accordance with DOT regulations.
*This corresponds to 85% by volume at 5°F and to 90.6% by volume at
60°F.
(b) The filling density for refrigerated storage tanks shall be such that the tanks will not be liquid full at a liquid temperature corresponding
to the vapor pressure at the start-to-discharge pressure setting of the pressure relief valve.
(c) If containers are to be filled according to liquid level by any gauging method other than a fixed length dip tube gauge, each container
shall have a thermometer well so that the internal liquid temperature can be easily determined and the amount of liquid and vapor in the container
corrected to a sixty (60) degrees Fahrenheit basis.