355 IAC 3-2-9

355 IAC 3-2-9 Filling densities

Last amended: 2025Year: 2027Length: 143 wordsOfficial source

Cite as Ind. Admin. Code tit. 355, r. 3-2-9

Sec. 9. (a) The filling densities for nonrefrigerated containers shall not exceed the following: Aboveground (1) Uninsulated 56%* (2) Insulated 57% (3) DOT containers shall be filled in accordance with DOT regulations. *This corresponds to 85% by volume at 5°F and to 90.6% by volume at 60°F. (b) The filling density for refrigerated storage tanks shall be such that the tanks will not be liquid full at a liquid temperature corresponding to the vapor pressure at the start-to-discharge pressure setting of the pressure relief valve. (c) If containers are to be filled according to liquid level by any gauging method other than a fixed length dip tube gauge, each container shall have a thermometer well so that the internal liquid temperature can be easily determined and the amount of liquid and vapor in the container corrected to a sixty (60) degrees Fahrenheit basis.