355 IAC 3-4-3
355 IAC 3-4-3 Installation of storage containers; aboveground; underground
Cite as Ind. Admin. Code tit. 355, r. 3-4-3
Sec. 3. (a) Containers shall be provided with substantial reinforced concrete footings and foundations or structural steel supports mounted
on reinforced concrete foundations. In either case, the reinforced concrete foundations or footings must extend below the established frost line and
shall be of sufficient width and thickness to support the total weight of the containers and contents adequately. The foundation shall maintain the
lowest point of the tank at not less than eighteen (18) inches above the ground. In lieu of footings, unitized, floating type foundations of sufficient
size may be used to adequately support the tank, contents, and piping.
(b) Horizontal containers shall be mounted on foundations in such a manner as to permit expansion and contraction. Every container shall
be supported so as to prevent the concentration of excessive loads on the supporting portion of the shell. Suitable means of preventing corrosion
shall be provided on that portion of the container in contact with the foundations or saddles.
(c) Secure anchorage or adequate pier height shall be provided against container flotation wherever high flood water might occur.
(d) Underground containers are prohibited.
(e) Distance between containers of over one thousand two hundred (1,200) gallons capacity shall be at least five (5) feet. Commonly
plumbed containers shall be installed such that the eighty-five percent (85%) liquid fill line of each container is at equal elevation.