170 IAC 4-1-8
170 IAC 4-1-8 Average accuracy of watthour meters; tests
Cite as Ind. Admin. Code tit. 170, r. 4-1-8
Sec. 8. (a) The accuracy at light load shall be determined at a load of approximately ten percent (10%) of the rated test amperes of the
meter. The accuracy at full load shall be determined at a load of one hundred percent (100%) of the rated test amperes of the meter. For meters used
with current transformers:
(1) full load shall be approximately one hundred percent (100%) of either the meter test amperes or the secondary current rating of
the current transformers; and
(2) light load shall be approximately ten percent (10%) of the selected full load current.
Average percentage registration is the average of the percentage registration at light load (LL) and at full load (FL). Thus, average percentage
accuracy = (FL + LL) ÷ 2.
(b) The accuracy at light load shall be determined by taking the average of at least two (2) tests, which tests must agree within one-half
of one percent (.5%) unless the meter has been tested by an automated device in which case one (1) test will be sufficient. The accuracy at full load
shall be determined in a like manner. The average accuracy of the meter shall be determined by taking an average of the accuracy at light load and
of the accuracy at full load. However, the average "as found" accuracy of a meter may be determined from one (1) light load test and one (1) full
load test if:
(1) such average accuracy is less than one hundred three percent (103%); and
(2) if such meter is to be adjusted.
(c) After any meter has been adjusted, the "as left" accuracy of the meter shall be determined by tests at each load as outlined in subsection
(b).