410 IAC 6-6-6
410 IAC 6-6-6 Community buildings; toilet and laundry facilities
Cite as Ind. Admin. Code tit. 410, r. 6-6-6
Sec. 6. (a) The community building of a mobile home community, when provided, shall be constructed in accordance with the electrical,
plumbing, and other building codes of the state and the municipal unit in which the community is located. Construction of the building must be in
accordance with a plan approved by the department as well as by the department of fire and building services.
(b) All exterior openings shall be covered with sixteen (16) mesh screen or equivalent during periods of the year when insects are
prevalent.
(c) Toilet and laundry rooms shall be constructed so that they can be well-lighted at all times. The laundry rooms shall have illumination
of at least forty (40) foot-candles on work areas such as washtubs, ironing boards, and sorting tables. The toilet rooms shall have illumination of
forty (40) foot-candles in front of mirrors.
(d) Sufficient hot water heating facilities shall be available so that the temperature of the hot water is maintained at a minimum of one
hundred twenty (120) degrees Fahrenheit at all times for laundry facilities.
(e) Laundry trays and automatic washers shall be connected to the sanitary sewer.
(f) Community buildings shall be located at least fifteen (15) feet from any mobile home or manufactured home.
(g) Community buildings shall be maintained in a clean and sanitary condition at all times.