410 IAC 6-7.1-29
410 IAC 6-7.1-29 Electrical distribution system
Cite as Ind. Admin. Code tit. 410, r. 6-7.1-29
Sec. 29. (a) After the effective date of this rule, all new wiring, lighting, and electrical hook-ups shall be installed in compliance with
675 IAC 17. Existing wiring, lighting, and electrical hook-ups shall be installed and maintained in a safe condition.
(b) Fifteen (15) and twenty (20) ampere, one hundred twenty-five (125) volt receptacles at sanitary facilities shall have approved ground
fault circuit interrupter protection.
(c) Electrical receptacles shall have wiring and circuit breakers or fuses sized to conform to the amperage of the receptacle they
supply.
(d) Switches, circuit breakers, receptacles, control equipment, and metering devices located in wet places or outside a building shall be
weatherproof.
(e) Splices in electrical wires in accessible locations shall be made in approved junction boxes.
(f) When underground conductors enter or leave a building or a trench, they shall have mechanical protection from physical damage. The
protection must be rigid conduit, intermediate metal conduit, rigid nonmetallic conduit, schedule 80 electrical plastic tubing, or other mechanical
means. Underground conductors in conduit shall be a minimum of eighteen (18) inches below finished grade. Underground conductors not in conduit
shall be a minimum of twenty-four (24) inches below finished grade.
(g) Electrical equipment and conductors shall not be attached to trees.