410 IAC 6-8.3-57
410 IAC 6-8.3-57 Separation distances
Cite as Ind. Admin. Code tit. 410, r. 6-8.3-57
Sec. 57. (a) All septic tanks, dosing tanks, lift stations, and soil absorption systems shall be located in accordance with Table I as follows:
Table I Separation Distances
Minimum Distance in Feet from Septic Tank and Other Treatment Units, Dosing Tank, Lift Station Soil
Absorption System
Private water supply well1,2 50 50
Private geothermal well1,2 50 50
Commercial water supply well1 100 100
Commercial geothermal well1 100 100
Public water supply well, lake,1, 3, 4 or reservoir1, 3, 4 200 200
Other pond, retention pond, lake, or reservoir3 50 50
Stormwater detention area3, 5 25 25
River, stream, ditch, or drainage tile6 25 25
Buildings, foundations, slabs, garages, patios, barns, aboveground and belowground swimming pools, retaining walls, closed loop
geothermal systems, roads, driveways, parking areas, or paved sidewalks 107 108
Front, side, or rear lot lines 5 5
Water lines continually under pressure 10 10
Suction water lines 50 50
Sinkhole 25 25
1 The distances enumerated shall be doubled for soil absorption systems constructed where there exist horizons, layers,
or strata within thirty-four (34) inches of the ground surface with a soil loading rate greater than seventy-five hundredths (0.75) gallons per day per
square foot as determined from Table IV of section 70(b)(8) of this rule, unless that hazard can be overcome through on-site sewage system
design.
2 The separation distance to a private water supply well abandoned in accordance with 312 IAC 13-10-2(e)
may be reduced to ten (10) feet.
3 Measured from the normal or ordinary high water mark.
4 See subsections (b) and (c).
5 Stormwater detention area: area designated for the temporary detention of stormwater, with the outlet located at the
lowest elevation of the depression.
6 See section 59(f) of this rule for subsurface drainage system separation.
7 Patios without footers, aboveground swimming pools, and sidewalks may be located within ten (10) feet of a septic tank,
as long as no required access points are obstructed.
8 A minimum separation of ten (10) feet is required on all sites.
(b) A residential on-site sewage system shall not be located within two hundred (200) feet of a public water supply lake or reservoir.
However, a residential on-site sewage system that includes secondary treatment may be less than two hundred (200) feet, but not less than fifty (50)
feet, from the normal or ordinary high water mark of the lake or reservoir if it:
(1) meets the minimum requirements of section 60(h)(1) through 60(h)(3) of this rule; or
(2) is a system component independent of the soil absorption field that meets the effluent quality requirements of NSF/ANSI for
certification under Standard 40 as a Class I plant, and that is approved by the department under the provisions of section 52(h) of this
rule.
(c) A residential on-site sewage system approved under the provisions of subsection (b) must be maintained for the life of the system
through an operating permit issued under the provisions of section 54 of this rule.
(d) Sewers shall not be located within fifty (50) feet of a water supply well or subsurface pump suction line, except as follows:
(1) Sewers constructed of waterworks grade ductile iron pipe with tyton or mechanical joints, or PVC pressure sewer pipe with an
SDR rating of twenty-six (26) or less with compression gasket joints, may be located within the fifty (50) foot distance.
(2) In no case shall sewers be located closer than twenty (20) feet to dug and bored water supply wells, or closer than ten (10) feet
to drilled and driven water supply wells or subsurface pump suction lines.
(e) Water lines and sewers shall not be laid in the same trench, as follows:
(1) A horizontal separation of ten (10) feet shall be maintained between water lines and sewers.
(2) Where crossings are necessary, a minimum of eighteen (18) inches vertical clearance must be maintained with the water line
positioned above the sewer line when possible.
(3) When it is impossible to maintain proper horizontal and vertical separation, the sewer shall be constructed of ductile iron pipe with
mechanical joints or PVC pressure sewer pipe with an SDR rating of twenty-six (26) or less, having mechanical or compression gasket joints within
ten (10) feet of the water line with the water line positioned above the sewer line when possible. The sewer shall be pressure tested to assure
watertightness prior to back filling.