170 IAC 4-5-7
170 IAC 4-5-7 Submeter accuracy
Cite as Ind. Admin. Code tit. 170, r. 4-5-7
Sec. 7. Submeter Accuracy. (a) Limits: No submeter that exceeds the test calibration limits for self-contained watt-hour meters as set by
the ANSI C12.1-1982, shall be placed in service or left in service. All electric current transformers, potential transformers, or other such devices
used in conjunction with submeters shall be considered part of the submeter and must also meet test calibrations and phase angle limits set by ANSI
C12.1-1982 and ANSI/IEEE C57.13-1978 for revenue billing. Whenever on installation, inspection, periodic, or other tests, a submeter or
transformer is found to exceed these limits, it shall be adjusted, repaired, or replaced.
(b) Adjustments: Submeters shall be adjusted as close as possible to the condition of zero error. The tolerances are specified only to allow
for necessary variations.