675 IAC 13-2.6-16

675 IAC 13-2.6-16 Chapter 14; exterior walls

Last amended: 2020Year: 2027Length: 183 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 13-2.6-16

Sec. 16. Chapter 14 is amended as follows: (a) Amend Section 1403.5, Vertical and lateral flame propagation, by adding an exception to read as follows: Exception: Buildings with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. (b) Amend Section 1405.3, Vapor retarders, by deleting in the first paragraph, "Chapter 3 of the International Energy Conservation Code" and inserting "the Indiana Energy Conservation Code". (c) Amend Section 1406.3, Balconies and similar projections as follows: (1) Insert after "floor construction", "or Section 711.3 for floors separating dwelling units". (2) Amend Exception 3, by inserting after "Type V construction", "unless projecting from floor/ceiling assemblies separating dwelling units" and, after "is", by inserting "provided throughout the building and". (d) Amend Section 1407.10.4, Full-scale tests, by adding an exception to read as follows: Exception: Buildings with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. (e) Delete Section 1408.6, Special inspections, without substitution. (f) Amend Section 1409.10.4, Full-scale tests, by adding an exception to read as follows: Exception: Buildings with automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2.