675 IAC 14-4.4-125
675 IAC 14-4.4-125 Section M2201.3; underground tanks
Cite as Ind. Admin. Code tit. 675, r. 14-4.4-125
Sec. 125. Delete the text of SECTION M2201.3 and substitute to read as follows:
Excavations for underground tanks shall not undermine the foundations of existing structures. Underground tanks shall be set on firm
foundations and surrounded with at least 6 inches (152.4 mm) of noncorrosive inert material, such as clean sand or gravel well tamped in place or
in accordance with the manufacturer's installation instructions. Tanks shall be covered with a minimum of 2 feet (609.6 mm) of earth or shall be
covered by not less than 1 foot (304.8 mm) of earth, on top of which shall be placed a slab of reinforced concrete not less than 4 inches (101.6 mm)
thick. When underground tanks are, or are likely to be, subjected to traffic, they shall be protected against damage from vehicles passing over them
by at least 3 feet (914.4 mm) of earth cover, or 18 inches (457.2 mm) of well-tamped earth plus 6 inches (152.4 mm) of reinforced concrete, or 8
inches (203.2 mm) of asphaltic concrete. When asphaltic or reinforced concrete paving is used as part of the protection, it shall extend at least 1 foot
(304.8 mm) horizontally beyond the outline of the tank in all directions. The clearance from the tank to the nearest wall of a basement, pit, or
property line shall not be less than 1 foot (305 mm). Corrosion protection shall be provided in accordance with Section
M2203.7.