675 IAC 14-4.4-134 Section G2411.2.6; separation

Last amended: 2025Year: 2027Length: 72 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 14-4.4-134

Sec. 134. Add SECTION G2411.2.6 to read as follows: SECTION G2411.2.6 SEPARATION. Except where connected to appliances and at bonding connections, corrugated stainless steel tubing that is not listed with an arc-resistant jacket or coating system in accordance with ANSI LC1/CSA 6.26 shall be isolated from metal gas piping, metal water piping, metal air ducts, metal structural framing, and all electrical wiring methods by a separation space of at least 2 inches.