675 IAC 14-4.4-24

675 IAC 14-4.4-24 Section R314.3.2; prohibited smoke alarm locations

Last amended: 2025Year: 2027Length: 70 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 14-4.4-24

Sec. 24. Add SECTION R314.3.2 to read as follows: SECTION R314.3.2 PROHIBITED SMOKE ALARM LOCATIONS. A smoke alarm required under this section shall not be placed: 1. within 3 feet (914 mm) horizontally from any grille moving conditioned air within the living space, or a door or opening of a bathroom containing a bathtub or shower; or 2. in any location or environment prohibited by the terms of the listing.