675 IAC 14-4.4-26

675 IAC 14-4.4-26 Section R314.8; visible notification appliances

Last amended: 2025Year: 2027Length: 122 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 14-4.4-26

Sec. 26. Add SECTION R314.8 to read as follows: SECTION R314.8 VISIBLE NOTIFICATION APPLIANCES. In addition to the smoke alarms required in this section, listed visible notification appliances, when installed, shall comply with the following: SECTION R314.8.1 CANDELA RATING – SLEEPING ROOM. A visible notification appliance, when installed in a room designed for sleeping, shall have a minimum rating of 177 candela, except that when the visible notification appliance is wall mounted or suspended more than 24 inches (610 mm) below the ceiling, a minimum rating of 110 candela is permitted. SECTION R314.8.2 CANDELA RATING – NONSLEEPING ROOM. A visible notification appliance, when installed in an area other than a room designed for sleeping, shall have a minimum rating of 15 candela.
675 IAC 14-4.4-26: 675 IAC 14-4.4-26 Section R314.8; visible notification appliances | Justis AI