675 IAC 14-4.4-78
675 IAC 14-4.4-78 Table R703.8.4(1); tie attachment and airspace requirements
Cite as Ind. Admin. Code tit. 675, r. 14-4.4-78
Sec. 78. Change TABLE R703.8.4(1) to read as follows:
TABLE R703.8.4(1)
TIE ATTACHMENT AND AIRSPACE REQUIREMENTS
BACKING AND TIE MINIMUM TIE
MINIMUM TIE FASTENERa AIRSPACEc
Wood stud backing with corrugated sheet metal 22
U.S. gage (0.0299 in.) x 7/8 in. wide 8d common nailb (2 1/2 in. x 0.131
in.) 3/4 in. minimum between sheathing and veneer
Wood stud backing with metal strand wire W1.7 (No.
9 U.S. gage; 0.148 in.) with hook embedded in mortar joint 8d common nailb (2
1/2 in. x 0.131 in.) 3/4 in. minimum between sheathing and veneer Maximum 4 1/2 in. between backing and veneer
Cold-formed steel stud backing with adjustable metal strand wire W1.7 (No. 9 U.S. gage; 0.148 in.) with hook embedded in mortar joint No. 10
screw extending through the steel framing a minimum of three exposed threads 3/4 in. minimum
between sheathing and veneer Maximum 4 1/2 in. between backing and
veneer
For SI: 1 inch = 25.4 mm.
a. In seismic
design category D0, D1, or D2, the minimum tie fastener shall be an 8d ring-shank nail (2 1/2 in. x 0.131
in.) or a No. 10 screw extending through the steel framing a minimum of three exposed threads.
b. All fasteners
shall have rust-inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to
corrosion.
c. Mortar is
permitted to encroach into the airspace or make incidental contact with the sheathing or the sheathing paper or equivalent.