675 IAC 14-4.4-83 Section R806.1; ventilation required
Cite as Ind. Admin. Code tit. 675, r. 14-4.4-83
Sec. 83. Add an EXCEPTION to SECTION R806.1 to read as follows:
EXCEPTION: Mechanical ventilation is permitted provided the following conditions are met:
1. The installation complies with manufacturer's instructions.
2. A humidistat is included with the installation.
3. An ammeter or equivalent device is installed in a readily visible location.