675 IAC 14-4.4-9
675 IAC 14-4.4-9 Section R302.11; fireblocking
Cite as Ind. Admin. Code tit. 675, r. 14-4.4-9
Sec. 9. Change the text of ITEM 4 of SECTION R302.11 to read as follows:
4. At openings around vents, pipes, ducts, cables, and wires at ceilings and floor level, with an approved material to resist the free
passage of flame and products of combustion. The material filling this annular space shall not be required to meet the ASTM E136 requirements
but shall have an ignition point at or above that of white pine wood, 350° F (177° C), and where surrounding electrical cables shall
meet the requirements of E3705.4.4.