675 IAC 14-4.4-92

675 IAC 14-4.4-92 Table N1102.1.4; equivalent U-factorsa

Last amended: 2025Year: 2027Length: 105 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 14-4.4-92

Sec. 92. Delete TABLE N1102.1.4 and substitute to read as follows: TABLE N1102.1.4 EQUIVALENT U-FACTORSa CLIMATE ZONE FENESTRATION U-FACTOR SKYLIGHT U-FACTOR CEILING U-FACTOR FRAME WALL U-FACTOR MASS WALL U-FACTORb FLOOR U-FACTOR BASEMENT WALL U-FACTOR CRAWL SPACE WALL U-FACTOR 4 0.35 0.60 0.030 0.082 0.141 0.047 0.059 0.065 5 0.35 0.60 0.030 0.067 0.082 0.033 0.059 0.065 a. Non-fenestration U-factors shall be obtained from measurement, calculation, or an approved source. b. When more than half the insulation is on the interior, the mass wall U-factors shall be a maximum of 0.10 in zone 4 and the same as the frame wall U-factor (0.057) in zone 5.