675 IAC 16-1.4-8
675 IAC 16-1.4-8 Chapter 7; sanitary drainage
Cite as Ind. Admin. Code tit. 675, r. 16-1.4-8
Sec. 8. Chapter 7 is amended as follows:
(a) Amend Table 704.1 as follows: delete "0.083.3 mm/m" and insert "83.3 mm/m".
(b) Amend Section 705.8.2 as follows: delete "purple" and "not purple in color and," without substitution.
(c) Amend Table 702.2 as follows: under "Copper or copper alloy tubing", delete without substitution "M or DWV".
(d) Amend Section 705.14.2 as follows: delete "purple" and "not purple in color and" without substitution.
(e) Amend Section 706.3 as follows: after "combination fittings", delete "side inlets or".
(f) Delete the fourth sentence in Section 708.3.5 without substitution.
(g) Amend Table 710.1(2) as follows: In the second column, delete "2,900" and insert "3,900".
(h) Add Section 710.3 to read as follows: 710.3 Minimum underground drainage size. The minimum pipe size installed underground
in a sanitary drainage system within a building shall be two (2) inch nominal (50.8 mm) pipe size.