675 IAC 17-1.8-15
675 IAC 17-1.8-15 Section 334.10; uses permitted
Cite as Ind. Admin. Code tit. 675, r. 17-1.8-15
Sec. 15. (a) Delete the text of (2) in Section 334.10 and substitute: (2) In any building or structure not exceeding three stories (see Section
362.10 for the definition of STORY).
(a) For exposed work except as prohibited in Section 334.12.
(b) Concealed within walls, floors, and ceilings except as prohibited in Section 334.12.
(b) Delete the text of (3) in Section 334.10 and substitute: (3) In any building or structure exceeding three stories (see Section 362.10 for
the definition of STORY), Type NM, Type NMC, and Type NMS cables shall be concealed within walls, floors, and ceilings that provide a thermal
barrier of material that has at least a 15-minute finish rating identified in listings of fire-rated assemblies. The 15-minute-finish-rated thermal barrier
shall be permitted to be used for combustible walls, floors, and ceilings, except as prohibited in Section 334.12.
Exception: Where the building is provided with an approved automatic sprinkler system throughout, Type NM, Type NMC, and Type
NMS cables are permitted to be used within walls, floors, ceilings, exposed or concealed, in buildings exceeding three
stories.