675 IAC 18-1.6-5

675 IAC 18-1.6-5 Chapter 4; ventilation

Last amended: 2020Year: 2027Length: 164 wordsOfficial source

Cite as Ind. Admin. Code tit. 675, r. 18-1.6-5

Sec. 5. (a) Amend Section 401.2 to add the letter "R" after "Section" and before "402.4.1.2". (b) Amend Section 401.4 by deleting "501.2.1" and inserting "501.3.1". (c) Delete Section 401.6 Contaminant sources in its entirety. (d) Amend Table 403.3 by adding the following table: Table 403.3 MINIMUM VENTILATION RATES OCCUPANCY CLASSIFICATION OCCUPANT DENSITY #/1000 FT2 a PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING ZONE, Rp CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN BREATHING ZONE, Ra CFM/ FT2 a EXHAUST AIRFLOW RATE CFM/ FT2 a Hotels, motels, resorts and dormitories Multipurpose assembly 120 5 0.06 - Bathrooms/toilets- privateg - - 25/50f Bedroom/living room 10 5 0.06 - Conference/meeting 50 5 0.06 - Dormitory sleeping areas 20 5 0.06 - Gambling casinos 120 7.5 0.18 - Lobbies/prefunction 30 7.5 0.06 - (e) Delete the text of Section 406.1, General, and insert the following: Uninhabited spaces, such as crawl spaces and attics, shall be provided with natural ventilation openings as required by the Indiana Building Code (675 IAC 13).