675 IAC 30-10-11
675 IAC 30-10-11 Stop valves and check valves
Cite as Ind. Admin. Code tit. 675, r. 30-10-11
Sec. 11. (a) If a heating boiler may be closed off from the heating system by closing a steam stop valve, there shall be a check valve in the
condensate return line between the boiler and the system.
(b) If any part of a heating system may be closed off from the remainder of the system by closing a steam stop valve, there shall be a check
valve in the condensate return pipe from that part of the system.