675 IAC 30-1-5
675 IAC 30-1-5 Exemptions from inspection
Cite as Ind. Admin. Code tit. 675, r. 30-1-5
Sec. 5. (a) Each of the following vessels must comply with the applicable requirements of the edition of the ASME B&PVC in effect
at the time of construction, but are exempt from inspection and operating permit requirements:
(1) Vessels located on a farm and used solely for agricultural purposes.
(2) Boilers meeting the requirements of clauses (A), (B), (C), and (D) as follows:
(A) Contain a volume less than one and one half (1 1/2) cubic feet.
(B) Operate entirely full of a liquid heat transfer fluid that will not vaporize at the operating temperature and atmospheric pressure.
(C) Have a gross output rating not exceeding three hundred thousand (300,000) Btus per hour.
(D) Are not located in a place of public assembly.
(3) Unfired pressure vessels that:
(A) contain only water under pressure for domestic supply purposes, including those containing air, if the compressed air serves only as
a cushion or as part of an airlift pumping system; and
(B) are located in a Class 2 structure as defined in IC 22-12-1-5 or a residential structure with less than seven (7)
apartments.
(4) Steam cleaner as defined in 675 IAC 30-4-49.
(b) Each of the following objects are covered under the scope of the permit for the system of which it is a part and does not require a
separate operating permit; however, the object must meet all other requirements of IC 22-15-6 and this article:
(1) Expansion tanks located within a system where the boiler in that system is regulated by this article.
(2) Hot water storage tanks that contain only water under pressure under the following conditions:
(A) Temperature not to exceed two hundred ten (210) degrees Fahrenheit.
(B) Protected from overpressure.
(3) Refrigeration vessels located in a skid-mounted unit where said unit is regulated by this article.