327 IAC 3-6-12
327 IAC 3-6-12 Slope requirements for gravity sewers
Cite as Ind. Admin. Code tit. 327, r. 3-6-12
Sec. 12. (a) Gravity sewers, when flowing full, shall be designed and constructed with slopes that shall result in average flow velocities
of not less than two (2) feet per second in accordance with the following:
Minimum Slopes
Pipe Diameter (inches) Minimum Slope
(percent)
8 0.40
10 0.28
12 0.22
14 0.17
15 0.15
16 0.14
18 0.12
21 0.10
24 0.08
27 0.067
30 0.058
33 0.052
36 0.046
39 0.041
42 0.037
(b) Oversized gravity sewers shall not be approved to justify using decreased slopes.
(c) The slope of a gravity sewer, between any two (2) manholes, shall be uniform across the distance from the outlet invert elevation of
the upstream pipe and the inlet invert elevation of the downstream pipe.
(d) Gravity sewers shall be provided with anchors to protect against damage from impact and erosion in accordance with the following:
(1) Slopes greater than twenty percent (20%) shall be provided with anchors spaced no more than thirty-six (36) feet on
center.
(2) Slopes greater than thirty-five percent (35%) shall be provided with anchors spaced no more than twenty-four (24) feet on
center.
(3) Slopes greater than fifty percent (50%) shall be provided with anchors spaced no more than sixteen (16) feet on
center.