Sec. 27. (a) The effective volume of a wet well shall not be greater than the volume created by the average daily flow in thirty (30)
minutes.
(b) The floor of a wet well shall have a minimum slope of forty-five (45) degrees to a hopper bottom.
(c) A wet well that is covered shall be vented to allow for the displacement of air due to the filling of the wet well.