327 IAC 3-6-27

327 IAC 3-6-27 Wet wells

Last amended: 2026Year: 2027Length: 72 wordsOfficial source

Cite as Ind. Admin. Code tit. 327, r. 3-6-27

Sec. 27. (a) The effective volume of a wet well shall not be greater than the volume created by the average daily flow in thirty (30) minutes. (b) The floor of a wet well shall have a minimum slope of forty-five (45) degrees to a hopper bottom. (c) A wet well that is covered shall be vented to allow for the displacement of air due to the filling of the wet well.