327 IAC 8-10-3
327 IAC 8-10-3 Booster pump connection
Cite as Ind. Admin. Code tit. 327, r. 8-10-3
Sec. 3. No customer shall cause or allow the installation or maintenance of a booster pump in a public water system unless a device is
installed to control operation of the booster pump when pressure to pump suction drops as follows:
(1) Wherever a fire suppression system has a booster pump installed only for fire suppression, it shall have an audible or visual alarm
to provide warning when flow occurs and a control valve shall be installed on the booster pump discharge to automatically throttle the flow as
necessary to maintain a minimum of ten (10) pounds per square inch, gauge, pump suction pressure.
(2) For all booster pumps other than those described in subdivision (1), a control device shall be installed to either prevent operation
of the booster pump, or else to automatically throttle flow to or from the booster pump as necessary to maintain a minimum of twenty (20) pounds
per square inch, gauge, pump suction pressure. The supplier of water may require that the control device be calibrated to maintain a higher than
twenty (20) pounds per square inch, gauge, pump suction pressure, where necessary to provide a minimum pressure of twenty (20) pounds per square
inch, gauge, throughout the pressure zone of the public water system distribution system to which the customer is connected.