327 IAC 8-10-5
327 IAC 8-10-5 Secondary sources of supply; installation of air gaps or other devices
Cite as Ind. Admin. Code tit. 327, r. 8-10-5
Sec. 5. (a) Customers shall construct an air gap, or install a reduced pressure principle backflow preventer or double check valve assembly, in accordance with section 7 of this rule, on the customer service line to:
(1) tanks used only to store water from the PWS for fire suppression that are constructed to maintain the bacteriological quality of the water, in compliance with 327 IAC 8-2.7; or
(2) secondary sources of supply that:
(A) use well water as the only private source of supply;
(B) are constructed to maintain the bacteriological quality of the water, in compliance with 327 IAC 8-2.7; and
(C) produce, without treatment, water meeting the drinking water quality standards enumerated in 327 IAC 8-2.7.
(b) Customers shall construct an air gap, or install a double check valve assembly or reduced pressure principle backflow preventer, in accordance with section 7 of this rule, for a fire sprinkler system, to prevent stagnant water from backflowing into the drinking water supply. For a fire sprinkler system with a chemical additive, customers shall install a reduced pressure principle backflow preventer to prevent the chemical additive backflowing into the drinking water supply.
(c) A secondary source of supply of a type other than those enumerated in subsections (a) and (b) must not be physically connected on the customer service line to or into the facility.