327 IAC 8-3.4-13
327 IAC 8-3.4-13 Backup provisions for production wells
Cite as Ind. Admin. Code tit. 327, r. 8-3.4-13
Sec. 13. (a) The following backup provisions shall apply to both a community public water system and a noncommunity public water system
having a pumping capacity greater than or equal to seventy (70) gallons per minute:
(1) The backup provisions shall be designed to provide system conformance with section 12 of this rule when the largest pump is out
of service.
(2) A system shall have one (1) or more backup wells designed to provide system conformance with section 12 of this
rule.
(b) Schools, correctional facilities, health care facilities, and agricultural labor camps, regardless of pumping capacity, must comply with
the requirements of subsection (a).