327 IAC 8-3.4-15

327 IAC 8-3.4-15 Discharge piping

Last amended: 2026Year: 2027Length: 89 wordsOfficial source

Cite as Ind. Admin. Code tit. 327, r. 8-3.4-15

Sec. 15. Discharge piping shall: (1) meet the material requirements of 327 IAC 8-3.2-8; (2) meet the installation requirements of 327 IAC 8-3.2-17; (3) have control valves and other accessories located above the pumphouse floor when the discharge piping is located above grade; and (4) be equipped with: (A) check valve; (B) shut off valve; (C) pressure gauge; (D) flow measuring equipment for individual or collective flow measurement; (E) smooth nosed sample tap installed where positive pressure is maintained; and (F) threaded or flanged port for maintenance and testing.