LAC 43:XIII.1129
LAC 43:XIII.1129. Compressor Stations: Pressure Limiting Devices [49 CFR 192.169]
Cite as La. Admin. Code tit. 43, pt. XIII, § 1129
A. Each compressor station must have pressure relief or other suitable protective devices of sufficient capacity and sensitivity to ensure that the maximum allowable operating pressure of the station piping and equipment is not exceeded by more than 10 percent. [49 CFR 192.169(a)]
B. Each vent line that exhausts gas from the pressure relief valves of a compressor station must extend to a location where the gas may be discharged without hazard. [49 CFR 192.169(b)]