LAC 43:XIII.1909. Customer Meter Installations: Operating Pressure [49 CFR 192.359]

Last amended: 2004Year: 2026Length: 88 wordsOfficial source

Cite as La. Admin. Code tit. 43, pt. XIII, § 1909

A. A meter may not be used at a pressure that is more than 67 percent of the manufacturer's shell test pressure. [49 CFR 192.359(a)] B. Each newly installed meter manufactured after November 12, 1970, must have been tested to a minimum of 10 psi (69 kPa) gage. [49 CFR 192.359(b)] C. A rebuilt or repaired tinned steel case meter may not be used at a pressure that is more than 50 percent of the pressure used to test the meter after rebuilding or repairing. [49 CFR 192.359(c)]