LAC 43:XIII.2309
LAC 43:XIII.2309. Test Requirements for Pipelines to Operate below 100 psi (689 kPa) Gauge [49 CFR 192.509]
Cite as La. Admin. Code tit. 43, pt. XIII, § 2309
A. Except for service lines and plastic pipelines, each segment of a pipeline that is to be operated below 100 psi (689 kPa) gage must be leak tested in accordance with the following. [49 CFR 192.509]
1. The test procedure used must ensure discovery of all potentially hazardous leaks in the segment being tested. [49 CFR 192.509(a)]
2. Each main that is to be operated at less than 1 psi (6.9 kPa) gage must be tested to at least 10 psi (69 kPa) gage and each main to be operated at or above 1 psi (6.9 kPa) gage must be tested to at least 90 psi (621 kPa) gage. [49 CFR 192.509(b)]