LAC 43:XIII.8505. Protective Enclosures [49 CFR 193.2905]
Cite as La. Admin. Code tit. 43, pt. XIII, § 8505
A. The following facilities must be surrounded by a protective enclosure:
1. storage tanks; [49 CFR 2905(a)(1)]
2. impounding systems; [49 CFR 2905(a)(2)]
3. vapor barriers; [49 CFR 2905(a)(3)]
4. cargo transfer systems; [49 CFR 2905(a)(4)]
5. process, liquefaction, and vaporization equipment; [49 CFR 2905(a)(5)]
6. control rooms and stations; [49 CFR 2905(a)(6)]
7. control systems; [49 CFR 2905(a)(7)]
8. fire control equipment; [49 CFR 2905(a)(8)]
9. security communications systems; and [49 CFR 2905(a)(9)]
10. alternative power sources. [49 CFR 2905(a)(10)]
B. The protective enclosure may be one or more separate enclosures surrounding a single facility or multiple facilities.
C. Ground elevations outside a protective enclosure must be graded in a manner that does not impair the effectiveness of the enclosure. [49 CFR 193.2905(b)]
D. Protective enclosures may not be located near features outside of the facility, such as trees, poles, or buildings, which could be used to breach the security. [49 CFR 193.2905(c)]
E. At least two accesses must be provided in each protective enclosure and be located to minimize the escape distance in the event of emergency. [49 CFR 193.2905(d)]
F. Each access must be locked unless it is continuously guarded. During normal operations, an access may be unlocked only by persons designated in writing by the operator. During an emergency, a means must be readily available to all facility personnel within the protective enclosure to open each access. [49 CFR 193.2905(e)]