LAC 43:XIII.915. Temperature Derating Factor (T) for Steel Pipe [49 CFR 192.115]

Last amended: 2004Year: 2026Length: 67 wordsOfficial source

Cite as La. Admin. Code tit. 43, pt. XIII, § 915

A. The temperature derating factor to be used in the design formula in §905 is determined as follows. Gas Temperature in Degrees Fahrenheit (Celsius) | Temperature Derating Factor (T) 250F (121C) or less | 1.000 300F (149C) | 0.967 350F (177C) | 0.933 400 F (204C) | 0.900 450F (232C) | 0.867 B. For intermediate gas temperatures, the derating factor is determined by interpolation. [49 CFR 192.115]