A. The station’s critical components that could be damaged or contaminated by inundation shall be: 1. elevated to a minimum of two foot above the 100-year flood elevation, or protected to such elevations including the use of a levee system; 2. readily accessible at all times unless permitted to be out of service for the period of inaccessibility; 3. graded around the station so as to lead surface drainage away from the station; 4. protected to prevent vandalism and entrance by animals or unauthorized persons. The pump station should be located within a secure area such as a locked building or fenced area; 5. labeled such that the pumps and valves in the station are tagged to correspond to the maintenance record and for proper identification.