LAC 51:XII.219

LAC 51:XII.219. Booster Pumps

Last amended: 2018Year: 2026Length: 167 wordsOfficial source

Cite as La. Admin. Code tit. 51, pt. XII, § 219

A. Booster pumps shall be located or controlled so that: 1. they will not produce negative pressure in their suction lines; 2. pumps taking suction from storage tanks shall be provided adequate net positive suction head; 3. pumps taking suction from ground storage tanks shall be equipped with automatic shutoffs or low pressure controllers as recommended by the pump manufacturer; 4. automatic or remote control devices shall have a range between the start and cutoff pressure which will prevent excessive cycling; and 5. a bypass is available. B. Inline Booster Pumps. In addition to the other requirements of this section, inline booster pumps shall: 1. be accessible for servicing and repairs; 2. maintain inlet pressure installed in the distribution system as required in §237.A of this Part under all operating conditions; 3. maintain at least 20 psig (140 kPa) in the suction line under all operating conditions with automatic shutoff or low pressure controller, unless otherwise acceptable to the state health officer; and 4. have a bypass.