LAC 51:XII.219
LAC 51:XII.219. Booster Pumps
Cite as La. Admin. Code tit. 51, pt. XII, § 219
A. Booster pumps shall be located or controlled so that:
1. they will not produce negative pressure in their suction lines;
2. pumps taking suction from storage tanks shall be provided adequate net positive suction head;
3. pumps taking suction from ground storage tanks shall be equipped with automatic shutoffs or low pressure controllers as recommended by the pump manufacturer;
4. automatic or remote control devices shall have a range between the start and cutoff pressure which will prevent excessive cycling; and
5. a bypass is available.
B. Inline Booster Pumps. In addition to the other requirements of this section, inline booster pumps shall:
1. be accessible for servicing and repairs;
2. maintain inlet pressure installed in the distribution system as required in §237.A of this Part under all operating conditions;
3. maintain at least 20 psig (140 kPa) in the suction line under all operating conditions with automatic shutoff or low pressure controller, unless otherwise acceptable to the state health officer; and
4. have a bypass.