LAC 51:XIV.721
LAC 51:XIV.721. Cleanout Clearances
Cite as La. Admin. Code tit. 51, pt. XIV, § 721
A. Small Pipe. Cleanouts smaller than 3-inches shall be so installed that there is a clearance of not less than 12 inches (305 mm) for the purpose of rodding.
B. Large Pipe. Cleanouts on 3-inch or larger pipes shall be so located that there is a clearance of not less than 18 inches (457 mm) for the purpose of rodding.