LAC 51:XIV.809. Limitations

Last amended: 2012Year: 2026Length: 84 wordsOfficial source

Cite as La. Admin. Code tit. 51, pt. XIV, § 809

A. The following limitations/requirements shall apply to indirect waste pipes. 1. Indirect waste piping exceeding 2 ft (610 mm) long shall be trapped. 2. The maximum length of the indirect waste to indirect waste receptor shall not exceed 15-feet (4527 mm). Should an indirect waste pipe exceed 15 feet in length, a local vent shall be provided at a maximum of every 15 feet in length. B. Cleaning. Indirect waste piping shall be so installed as to permit ready access for flushing and cleansing.