A. Upon installation of any new fire sprinkler system, the system shall have a placard permanently affixed on each riser. The installation placard shall be a minimum of 2 3/4 inches by 2 3/4 inches. Maximum size cannot exceed 5 inches by 5 inches. The following information and wording shall be required to be preprinted on the front side of the tag:
1. DO NOT REMOVE BY ORDER OF THE STATE FIRE MARSHAL (all capital letters, in bold type);
2. installation placard;
3. installation date;
4. firm's name;
5. firm's certificate number;
6. qualifier's name;
7. qualifier's license number;
8. NFPA Code Edition System was installed under;
9. plan review or exemption number;
10. model number and manufacturer of sprinkler valve;
11. model number and date of each type of sprinkler head on system.
B. If after initial installation a sprinkler system is redesigned because of an occupancy change or the main control valve is replaced for any reason, a new installation placard shall be completed and attached as above, noting the appropriate changes in information.