LAC 33:V.3017. Small Quantity On-Site Burner Exemption
Cite as La. Admin. Code tit. 33, pt. V, § 3017
A. Exempt Quantities. Owners and operators of facilities that burn hazardous waste in an on-site boiler or industrial furnace are exempt from the requirements of this Chapter provided that:
1. the quantity of hazardous waste burned in a device for a calendar month does not exceed the limits provided in the following table based on the terrain-adjusted effective stack height as defined in LAC 33:V.3013.B.3:
Exempt Quantities for Small Quantity Burner Exemption
Terrain-Adjusted Effective Stack Height of Device (meters) | Allowable Hazardous Waste Burning Rate (gallons/ month)
0 to 3.9 | 0
4.0 to 5.9 | 13
6.0 to 7.9 | 18
8.0 to 9.9 | 27
10.0 to 11.9 | 40
12.0 to 13.9 | 48
14.0 to 15.9 | 59
16.0 to 17.9 | 69
18.0 to 19.9 | 76
20.0 to 21.9 | 84
22.0 to 23.9 | 93
24.0 to 25.9 | 100
26.0 to 27.9 | 110
28.0 to 29.9 | 130
30.0 to 34.9 | 140
35.0 to 39.9 | 170
40.0 to 44.9 | 210
45.0 to 49.9 | 260
50.0 to 54.9 | 330
55.0 to 59.9 | 400
60.0 to 64.9 | 490
65.0 to 69.9 | 610
70.0 to 74.9 | 680
75.0 to 79.9 | 760
80.0 to 84.9 | 850
85.0 to 89.9 | 960
90.0 to 94.9 | 1,100
95.0 to 99.9 | 1,200
100.0 to 104.9 | 1,300
105.0 to 109.9 | 1,500
110.0 to 114.9 | 1,700
115.0 or greater | 1,900
2. the maximum hazardous waste firing rate does not exceed at any time 1 percent of the total fuel requirements for the device (hazardous waste plus other fuel) on a total heat input or mass input basis, whichever results in the lower mass feed rate of hazardous waste;
3. the hazardous waste has a minimum heating value of 5,000 Btu/lb, as generated; and
4. the hazardous waste fuel does not contain (and is not derived from) EPA Hazardous Waste Numbers F020, F021, F022, F023, F026, or F027.
B. Mixing with Nonhazardous Fuels. If hazardous waste fuel is mixed with a nonhazardous fuel, the quantity of hazardous waste before such mixing is used to comply with Paragraph A.1 of this Section.
C. Multiple Stacks. If an owner or operator burns hazardous waste in more than one on-site boiler or industrial furnace exempt under this Section, the quantity limits provided by Paragraph A.1 of this Section are implemented according to the following equation.
where:
n = the number of stacks
Actual Quantity Burned = the waste quantity burned per month in device “i”
Allowable Quantity Burned = the maximum allowable exempt quantity for stack “i” from the table in LAC 33:V.3017.A.1
NOTE: Hazardous wastes that are subject to the special requirements for very small quantity generators under LAC 33:V.1009 may be burned in an off-site device under the exemption provided by LAC 33:V.3017, but must be included in the quantity determination for the exemption.
D. Notification Requirements. The owner or operator of facilities qualifying for the small quantity burner exemption under this Section must provide a one-time signed, written notice to the administrative authority indicating the following:
1. the combustion unit is operating as a small quantity burner of hazardous waste;
2. the owner or operator is in compliance with the requirements of this Section; and
3. the maximum quantity of hazardous waste that the facility may burn per month as provided by LAC 33:V.3017.A.1.
E. Recordkeeping Requirements. The owner or operator must maintain at the facility for at least three years sufficient records documenting compliance with the hazardous waste quantity, firing rate, and heating value limits of this Section. At a minimum, these records must indicate the quantity of hazardous waste and other fuel burned in each unit per calendar month, and the heating value of the hazardous waste.