LAC 33:V.30589

LAC 33:V.30589. What corrosion control information do I have to maintain? [49 CFR 195.589]

Last amended: 2003Year: 2026Length: 158 wordsOfficial source

Cite as La. Admin. Code tit. 33, pt. V, § 30589

A. You must maintain current records or maps to show the location of: [49 CFR 195.589(a)] 1. cathodically protected pipelines; [49 CFR 195.589(a)(1)] 2. cathodic protection facilities, including galvanic anodes, installed after January 28, 2002; and [49 CFR 195.589(a)(2)] 3. neighboring structures bonded to cathodic protection systems. [49 CFR 195.589(a)(3)] B. Records or maps showing a stated number of anodes, installed a stated manner or spacing, need not show specific distances to each buried anode. [49 CFR 195.589(b)] C. You must maintain a record of each analysis, check, demonstration, examination, inspection, investigation, review, survey, and test required by this Subchapter in sufficient detail to demonstrate the adequacy of corrosion control measures or that corrosion requiring control measures does not exist. You must retain these records for at least five years, except that records related to §§30569, 30573.A and B, and 30579.B.3 and C must be retained for as long as the pipeline remains in service. [49 CFR 195.589(c)]