LAC 33:XV.1747

LAC 33:XV.1747. Pool Water Purity

Last amended: 1998Year: 2026Length: 90 wordsOfficial source

Cite as La. Admin. Code tit. 33, pt. XV, § 1747

A. Pool water purification systems shall be run sufficiently to maintain the conductivity of the pool water below 20 microsiemens per centimeter under normal circumstances. If pool water conductivity rises above 20 microsiemens per centimeter, the licensee shall take prompt actions to lower the pool water conductivity and shall take corrective actions to prevent future recurrences. B. The licensee shall measure the pool water conductivity frequently, but no less than weekly, to assure that the conductivity remains below 20 microsiemens per centimeter. Conductivity meters shall be calibrated at least annually.
LAC 33:XV.1747: LAC 33:XV.1747. Pool Water Purity | Justis AI