310 CMR 15.224
Multiple Compartment Tanks
Tanks with multiple compartments shall be required as specified in 310 CMR 15.223(1).
When multiple compartment tanks are used the following shall be required:
(1) The number of compartments shall not exceed two;
(2) The first compartment shall be sized for a minimum hydraulic detention time of 48 hours
based on the design flow;
(3) The second compartment shall be sized for a minimum hydraulic detention time of 24 hours
based on the design flow;
(4) The compartments shall be interconnected by a minimum four inch vented, inverted
U-shaped pipe which extends below the bottom of the scum layer; and
(5) The outlet tee of each compartment shall be equipped with a corrosion resistant gas baffle
or a Department approved effluent tee filter.