310 CMR 15.227
Placement and Construction of Tees
(1) Inlet and outlet tees shall be Schedule 40 PVC and shall extend a minimum of six inches
above the flow line of the septic tank and be on the center line of the septic tank located directly
under the clean-out manhole. Tranverse flow baffles shall not be used as substitutes for inlet or
outlet tees.
(2) The minimum separation between inlet and outlet tees shall be no less than the liquid depth
of the septic tank and shall be the longest direction (which shall not include the diagonal
distance) across the tank in plan view.
(3) Inlet and outlet tees to rectangular tanks shall be set in the end walls or into a side wall
within 12 inches of the end wall. For circular tanks, the inlet and outlet tees shall be set and
stabilized on opposite ends of a diameter of the tank.
(4) There shall be an air space of at least three inches between the tops of the tees and the inside
of the tank cover. The tops of the tees shall be left open to provide ventilation or separate
ventilation shall be provided. All outlet tees shall be equipped with a gas baffle or a Department
approved effluent tee filter.
(5) The inlet pipe elevation shall be no less than two inches nor more than three inches above
the invert elevation of the outlet pipe. The inlet and outlet invert elevations shall be at least 12
inches above the high groundwater elevation. If high groundwater (redoximorphic features) is
determined by soil evaluation in accordance with 310 CMR 15.100 through 15.107 at the
proposed location of the septic tank, the Approving Authority may reduce the 12 inch required
separation, but in no cases shall it be reduced to less than one inch above high groundwater as
determined by redoximorphic features.
(6) The inlet tee shall extend a minimum of ten inches below the flow line. The outlet shall be
provided with a tee extending below the flow line in accordance with the following table:
Liquid Depth in Septic Tank
Depth of Outlet Tee below Flow Line
4 feet
14 inches
5 feet
19 inches
6 feet
24 inches
7 feet
29 inches
8 feet
34 inches
(7) Effluent tee filters may be installed in lieu of outlet tees provided that they are installed in
accordance with the manufacturer’s specifications, include an appropriate outlet cover at grade,
and are inspected and cleaned at least on an annual basis.