310 CMR 15.252
Beds or Fields
(1) The use of leaching beds or fields is restricted to systems with a calculated design flow of
less than 5,000 gpd per leaching bed or field.
(2) Bed or field specifications:
(a) Minimum number of distribution lines = 2.
(b) Length - 100 feet maximum.
(c) Slope of distribution lines - 0.005 feet per foot.
(d) Separation distance between lines - six feet maximum.
(e) Lateral separation distance between lines and edge of the bed - four feet maximum.
(f) Separation distance between adjacent beds/fields - ten feet.
(g) Aggregate depth (below the invert of the distribution lines) - six inches minimum, 12
inches maximum.
(h) Distribution lines - refer to 310 CMR 15.251(5) through (10) (Trenches).
(i) Effective leaching area - shall include only the bottom area, not the sidewalls.