310 CMR 22.06A
Special Monitoring for Sodium, Reporting and Analytical Methods and Frequency
(1) Monitoring. All public water systems (community, non-transient non-community and
transient non-community) shall monitor for the determination of sodium concentration levels.
(2) Initial Sampling Frequency. Each community, non-transient, non-community and transient
non-community water system is required to monitor for sodium during the first three-year
compliance period of each nine-year compliance cycle beginning in the compliance period
starting January 1, 1993.
(a) GW Sampling Frequency. Groundwater systems shall take one sample at each sampling
point during each compliance period beginning in the compliance period starting
January 1, 1993, (once every three years).
(b) SW Sampling Frequency. Surface water systems (or combined surface/ground) shall
take one sample annually at each sampling point beginning January 1, 1993.
(3) Sampling Protocol. Monitoring shall be conducted as follows:
(a) Ground Water Sampling Points. Groundwater systems shall take a minimum of one
sample at every entry point to the distribution system which is representative of each well
after treatment (sampling point) beginning in the compliance period starting January 1, 1993.
The system shall take each sample at the same sampling point unless conditions make
another sampling point more representative of each source or treatment plant.
(b) Surface Water Sampling Points. Surface water systems (Note: For purposes of
310 CMR 22.06A(3)(b), surface water systems include systems with a combination of
surface and ground sources.) shall take a minimum of one sample at every entry point to the
distribution system after any application of treatment or in the distribution system at a point
which is representative of each source after treatment (sampling point) beginning in the
compliance period beginning January 1, 1993. The system shall take each sample at the
same sampling point unless conditions make another sampling point more representative of
each source or treatment plant.
22.06A: continued
(c) Multiple Sources. If a system draws water from more than one source and the sources
are combined before distribution, the system must sample at an entry point to the distribution
system during periods of normal operating conditions (i.e., when water is representative of
all sources being used).
(4) Sodium Reporting. The supplier of water shall report to the Department the results of the
analyses for sodium within the first ten days of the month following the month in which the
sample results were received or within the first ten days following the end of the required
monitoring period, whichever comes first.
(5) Sodium Notification. The supplier of water shall report the level of sodium for each source
to the local Boards of Health and Massachusetts Department of Public Health by written notice
by direct mail within 30 days after the supplier of water first learns of the analytic results which
indicate a level of sodium.
(6) Sampling Schedules. Each public water system shall monitor at the time designated by the
Department during each compliance period.
(7) Sodium Analysis Analytical Methods. Analysis for sodium shall be conducted using the
following method:
SODIUM ANALYTICAL METHODS
Reference (Method Number)
Contaminant
Methodology
EPA
SM
Sodium
Inductively-coupled Plasma
--
Atomic absorption;
direct aspiration
--
3111B
Methods for the Determination of Metals in Environmental Samples - Supplement I", EPA-600/r-94/111,
May 1994. Available at NTIS, PB-95-125472.
Standard Methods for the Examination of Water and Wastewater", 18 and 19 edition, American Public
th
th
Health Association, 1992 and 1995, only - not the 20 edition.
th
For approved analytical procedures for metals, the technique applicable to total metals must be used.
Standard Methods Online are available at
http://www.standardmethods.org. The year in which each
method was approved by the Standard Methods Committee is designated by the last two digits in the
method number. The methods listed are the only online versions that may be used.