310 CMR 22.07D
Chemical Standards
(1) Secondary Contaminants. The following contaminant levels apply to every public water
systems:
Contaminant
Secondary MCL
(a) Aluminum
0.05 to 0.2 mg/l
(b) Chloride
250 mg/l
(c) Color
15 Color Units
(d) Copper
1 mg/l
(e) Corrosivity
Non-corrosive
(f) Fluoride
2.0 mg/l
(g) Foaming Agents
0.5 mg/l
(h) Iron
0.3 mg/l
(i) Manganese
0.05 mg/l
(j) Odor
3 Threshold Unit Number
(k) pH
6.5 – 8.5
(l) Silver
0.10 mg/l
(m) Sulfate
250 mg/l
(n) Total Dissolved Solids
500 mg/l
(o) Zinc
5 mg/l
(2) Monitoring for Secondary Contaminants. The monitoring frequency for the contaminants
listed in 310 CMR 22.07D(1) is at the discretion of the Department.
(3) Exceeding a Secondary Maximum Contaminant Level. If the Department finds based on
a health evaluation by the Department's Office of Research and Standards, that an SMCL
exceedance, acting alone or in combination with other contaminants, poses an unacceptable
health risk to consumers, the public water system shall take all actions necessary to reduce the
SMCL concentrations to levels the Department deems safe by the deadline specified by the
Department. Such public water system shall also monitor the water and provide public notice
as directed by the Department and notify the Department in writing of its proposed actions.
(4) The analytical methods for Secondary Contaminants are available in the Federal
Register/Vol.72, No. 47/March 12, 2007.