310 CMR 22.20A
Surface Water Treatment Rule
(1) General Requirements.
(a) 310 CMR 22.20A establishes criteria under which Filtration is required as a Treatment
Technique for Public Water Systems supplied by Surface Water Sources and groundwater
sources under the direct influence of surface water. In addition, 310 CMR 22.20A
establishes Treatment Technique requirements in lieu of Maximum Contaminant Levels for
the following contaminants:
1. Giardia lamblia;
2. Viruses;
3. Heterotrophic plate count bacteria;
4. Legionella; and
5. Turbidity.
(b) Each Supplier of Water with a Surface Water Source, or groundwater source under the
direct influence of surface water, must provide treatment of that source water that complies
with the Treatment Technique requirements set forth in 310 CMR 22.20A. The Treatment
Technique requirements consist of installing and properly operating water treatment
processes which reliably achieve:
1. At least 99.9% (3 log) removal and/or inactivation of Giardia lamblia cysts between
a point where the Raw Water is not subject to recontamination by Surface Water runoff
and a point downstream before or at the first customer; and
2. At least 99.99% (4 log) removal and/or inactivation of Viruses between a point
where the Raw Water is not subject to recontamination by Surface Water runoff and a
point downstream before or at the first customer.
(c) A Supplier of Water using a Surface Water Source or groundwater source under the
direct influence of surface water shall be deemed in compliance with the requirements of
310 CMR 22.20A(1)(a) and (b) if:
1. It meets the requirements for avoiding Filtration in 310 CMR 22.20A(2) and the
Disinfection requirements in 310 CMR 22.20A(3)(a); or
2. It meets the Filtration requirements in 310 CMR 22.20A(4) and the Disinfection
requirements in 310 CMR 22.20A(3)(b).
(d) Each Supplier of Water using a Surface Water Source or a groundwater source under
the direct influence of surface water must be operated by a Certified Operator in compliance
with 310 CMR 22.11B.
(e) In addition to complying with requirements of 310 CMR 22.20A, systems serving at
least 10,000 people shall also comply with the requirements of 310 CMR 22.20D.
22.20A: continued
(f) In addition to complying with the requirements of 310 CMR 22.20A, each Supplier of
Water that serves fewer than 10,000 people must also comply with the requirements in
310 CMR 22.20F.
(2) Criteria for Avoiding Filtration. A Supplier of Water that uses a Surface Water Source
must meet all of the conditions in 310 CMR 22.20A(2)(a) and (b) and is subject to 310 CMR
22.20A(2)(c) beginning June 29, 1991, unless the Department has notified it in writing that
Filtration is required. A Supplier of Water that uses a groundwater source under the direct
influence of surface water must meet all of the conditions in 310 CMR 22.20A(2)(a) and (b) and
is subject to 310 CMR 22.20A(2)(c) beginning 18 months after the Department determines that
it is under the direct influence of surface water, or June 29, 1991, whichever is later, unless the
Department has notified it in writing that Filtration is required. If the Department determines
in writing, before June 29, 1991 that Filtration is required, the Supplier of Water must have
installed Filtration and meet the criteria for filtered systems specified in 310 CMR 22.20A(3)(b)
and (4) by June 29, 1993. Within 18 months of the failure of a system using a Surface Water
Source or a groundwater source under the direct influence of surface water to meet any one of
the requirements in 310 CMR 22.20A(2)(a) and (b) or after June 29, 1993, whichever is later,
the Supplier of Water must have installed Filtration and meet the criteria for filtered systems
specified in 310 CMR 22.20A(3)(b) and (4).
(a) Source Water Quality Conditions.
1. The fecal coliform concentration must be equal to or less than 20/100 ml, or the total
coliform concentration must be equal to or less than 100/100 ml (measured as specified
in 310 CMR 22.20A(5)(a)1. and (b)1. in representative samples of the source water
immediately prior to the first or only Point of Disinfectant Application in at least 90%
of the measurements made for the six previous months that the system served water to
the public on an ongoing basis. If a system measures both fecal and total coliform, the
fecal coliform criterion, but not the total coliform criterion, in 310 CMR 22.20A(2)(a)1.
must be met.
2. The Turbidity level cannot exceed one NTU (measured as specified in 310 CMR
22.20A(5)(a)1. and (b)2. in representative samples of the source water immediately prior
to the first or only Point of Disinfectant Application except that five or fewer Turbidity
units may be allowed if the Supplier of Water can demonstrate to the Department that
the higher Turbidity does not do any of the following:
a. Interfere with Disinfection.
b. Prevent maintenance of an effective Disinfectant agent throughout the
Distribution System; or
c. Interfere with microbiological determinations.
3. The Turbidity level cannot exceed five NTU (at any time) unless:
a. The Department determines that any such event was caused by circumstances
that were unusual and unpredictable; and
b. As a result of any such event, there have not been more than two events in the
past 12 months the system served water to the public, or more than five events in the
past 120 months the system served water to the public, in which the Turbidity level
exceeded five NTU. An "event" is a series of consecutive days during which at least
one Turbidity measurement each day exceeds five NTU.
(b) Site Specific Conditions.
1. A Supplier of Water must meet the requirements of 310 CMR 22.20A(3)(a)1. at
least 11 of the 12 previous months that its system served water to the public on an
ongoing basis, unless the system fails to meet the requirements during two of the 12
previous months that the system served water to the public, and the Department
determines that at least one of the failures was caused by circumstances that were
unusual and unpredictable.
2. A Supplier of Water must meet the requirements of 310 CMR 22.20A(3)(a)2. at all
times its system serves water to the public unless otherwise approved by the
Department.
3. A Supplier of Water must meet the requirements of 310 CMR 22.20A(3)(a)3. at all
times its system serves water to the public unless the Department determines that any
such failure was caused by circumstances that were unusual and unpredictable.
22.20A: continued
4. A Supplier of Water must meet the requirements of 310 CMR 22.20A(3)(a)4. on an
ongoing basis, unless the Department determines that any such failure was not caused
by a deficiency in treatment of the source water.
5. A Supplier of Water must maintain a Watershed Protection/Control Program that
adequately minimizes the potential for contamination by Giardia lamblia cysts,
Cryptosporidium oocysts and Viruses. During onsite inspection, the Department will
determine whether the Watershed Protection/Control Program is adequate to minimize
the potential for contamination by Giardia lamblia cysts, Cryptosporidium oocysts and
Viruses in the source water. The adequacy of the Watershed Protection/Control
Program to prevent potential contamination of the source water and other contaminants
must be based on:
a. The comprehensiveness of the watershed review;
b. The effectiveness of the system's program to monitor and control detrimental
activities occurring in the Watershed; and
c. Extent to which the water system has maximized land ownership and/or
controlled land use within the Watershed.
d. At a minimum, a Watershed Protection/Control Program shall include the
following information:
i. a Watershed description, including maps and accompanying narratives of
major physical features, components of the water system, and hydrological
characteristics;
ii. the Watershed characteristics and activities which may have an adverse
effect on source water quality;
iii. a risk assessment and plan for controlling detrimental activities/events that
may have an adverse impact on source water quality;
iv. a plan for monitoring Raw Water quality parameters at locations vulnerable
to contamination from detrimental activities;
v. demonstrated control through land ownership and/or land use restrictions on
all human activities within the Watershed which may have an adverse impact on
the microbiological quality of the source water; and
vi. a management plan for staffing, training and maintaining effective day to
day operations (including Emergency response to contamination) and
implementing a Department-approved Watershed Control/Protection Program.
vii. a description of activities in the Watershed that affect water quality,
projects what adverse activities are expected to occur in the future, describes
how the Supplier of Water expects to address them and otherwise complies with
310 CMR 22.20B(9) and 22.21(4), if applicable.
e. The Supplier of Water shall submit an annual report on Department-approved
forms to the Department. The annual report shall identify any special concerns
about the Watershed and how they are being handled;
6. The Supplier of Water shall be subject to an annual on site inspection by the
Department or a Person designated by the Department to assess the Watershed
Protection/Control Program and Disinfection treatment process. A report of the on site
inspection which summarizes all findings must be prepared every year. The on site
inspection must indicate to the Department's satisfaction that the Watershed Protection/
Control Program and Disinfection treatment process are adequately designed and
maintained. The on site inspection must include:
a. A review of the effectiveness of the Watershed Protection/Control Program Plan;
b. A review of the physical condition of the source intake and how well it is
protected;
c. A review of the system's equipment maintenance program to ensure there is low
probability for failure of the Disinfection process;
d. An inspection of the Disinfection equipment for physical deterioration;
e. A review of operating procedures;
f. A review of data records to ensure that all required tests are being conducted and
recorded and Disinfection is effectively practiced; and
g. Identification of any improvements which are needed in the equipment, system
maintenance and operation, or data collection.
22.20A: continued
7. The Public Water System must not have been identified as a source of a Waterborne
Disease Outbreak, or if it has been so identified, the system must have been modified
sufficiently to prevent another such occurrence, as determined by the Department.
8. A Supplier of Water must comply with the Maximum Contaminant Level (MCL)
for E. coli in 310 CMR 22.05(8) at least 11 months of the 12 previous months that the
system served water to the public, on an ongoing basis, unless the Department
determines that failure to meet this requirement was not caused by a deficiency in
treatment of the source water.
9. Each Supplier of Water shall comply with the requirements for Trihalomethanes in
310 CMR 22.07(1) and (2) until December 31, 2001. After January 1, 2002, the Public
Water System shall comply with the requirements for Total Trihalomethanes, Haloacetic
Acids (Five), bromate, chlorite, chlorine, chloramines and chlorine dioxide as
appropriate or applicable depending on Disinfectant used and in accordance with
310 CMR 22.07E.
(c) Treatment Technique Violations.
1. A Supplier of Water shall be deemed in violation of a Treatment Technique
requirement if it:
a. fails to meet any one of the criteria in 310 CMR 22.20A(2)(a) or (b) and/or
which the Department has notified in writing that Filtration is required; or
b. fails to install Filtration by the date specified in 310 CMR 22.20A(2).
2. A Supplier of Water that has not installed Filtration is in violation of a Treatment
Technique requirement if:
a. the Turbidity level (measured as specified in 310 CMR 22.20A(5)(a)1. and (b)2.)
in a representative sample of the source water immediately prior to the first or only
point of Disinfection exceeds one NTU unless five or fewer NTU units have been
allowed by the Department; or
b. its system is identified as a source of a Waterborne Disease Outbreak.
(3) Disinfection. A Supplier of Water that uses a Surface Water Source and does not provide
Filtration treatment must provide the Disinfection treatment specified in 310 CMR 22.20A(3)(a)
beginning December 29, 1991, unless the Department notifies it in writing that Filtration is
required. A Supplier of Water that uses a groundwater source under the direct influence of
surface water and does not provide Filtration treatment must provide Disinfection treatment
specified in 310 CMR 22.20A(3)(a) beginning December 29, 1991, or 18 months after the
Department determines that the groundwater source is under the influence of surface water,
whichever is later, unless the Department has notified it in writing that Filtration is required.
If the Department has determined that Filtration is required, the Supplier of Water must comply
with any interim Disinfection requirements the Department deems necessary before Filtration
is installed. A Supplier of Water that uses a Surface Water Source that provides Filtration
treatment must provide the Disinfection treatment specified in 310 CMR 22.20A(3)(b)
beginning June 29, 1993, or beginning when Filtration is installed, whichever is later. A
Supplier of Water that uses a groundwater source under the direct influence of surface water and
provides Filtration treatment must provide Disinfection treatment as specified in 310 CMR
22.20A(3)(b) by June 29, 1993, or beginning when Filtration is installed, whichever is later.
Failure to meet any requirement in 310 CMR 22.20A(3) after the applicable date is a Treatment
Technique violation.
(a) Disinfection requirements for Public Water Systems that do not provide Filtration. A
Supplier of Water that does not provide Filtration treatment must provide Disinfection
treatment as follows:
1. The Disinfection treatment must be sufficient to ensure at least 99.9% (3 log)
inactivation of Giardia lamblia cysts and 99.99% (4 log) inactivation of Viruses, every
day the system serves water to the public, except any one day each month. Each day a
system serves water to the public, the Supplier of Water must calculate the CT value(s)
from the system's treatment parameters, using the procedure specified in 310 CMR
22.20A(5)(b)3., and determine whether this value(s) is sufficient to achieve the specified
inactivation rates for Giardia lamblia cysts and Viruses. If a system uses a Disinfectant
other than chlorine, the Supplier of Water may demonstrate to the Department, through
the use of a Department approved protocol for on site Disinfection challenge studies or
other information satisfactory to the Department, that CT99.9 values other than those
specified in 310 CMR 22.20A(5)(b)3.: Tables 2.1 and Table 3.1 in or other operational
parameters are adequate to demonstrate that the system is achieving the minimum
inactivation rates required by 310 CMR 22.20A(3)(a).
22.20A: continued
2. The Disinfection system must have redundant components, including an auxiliary
power supply with automatic start up and alarm to ensure that Disinfectant application
is maintained continuously while water is being delivered to the Distribution System
unless otherwise approved by the Department.
3. The Residual Disinfectant Concentration in the water entering the Distribution
System, measured as specified in 310 CMR 22.20A(5)(a)2. and (b)5., cannot be less
than 0.2 mg/l for more than four hours.
4. The Residual Disinfectant Concentration in the Distribution System measured as
free chlorine, total chlorine, combined chlorine, or chlorine dioxide, as specified in
310 CMR 22.20A(5)(a)2. and (b)6., cannot be undetectable in more than 5% of the
samples each month, for any two consecutive months that the system serves water to the
public. Water in the Distribution System with a heterotrophic bacteria concentration
less than or equal to 500/ml, measured as heterotrophic plate count (HPC) as specified
in 310 CMR 22.20A(5)(a)1., is deemed to have a detectable Disinfectant residual for
purposes of determining compliance with this requirement. Thus, the value "V" in the
following formula cannot exceed 5% in one month, for any two consecutive months.
Where:
a = number of instances where the Residual Disinfectant Concentration is measured;
b = number of instances where the Residual Disinfectant Concentration is not
measured but heterotrophic bacteria plate count (HPC) is measured;
c = number of instances where the Residual Disinfectant Concentration is measured
but not detected and no HPC is measured;
d = number of instances where the Residual Disinfectant Concentration is measured
but not detected and where the HPC is >500/ml; and
e = number of instances where the Residual Disinfectant Concentration is not
measured and HPC is >500/ml.
(b) Disinfection Requirements for Public Water Systems Which Provide Filtration. A
Supplier of Water that provides Filtration treatment must provide Disinfection treatment as
follows:
1. a. The Disinfection treatment must be sufficient to ensure that the total treatment
processes of that system achieve at least 99% (2-log) removal of Cryptosporidium,
at least 99.9% (3 log) inactivation and/or removal of Giardia lamblia cysts and at
least 99.99% (4 log) inactivation and/or removal of Viruses, as determined by the
Department.
b. Failure to provide this Disinfection treatment on a daily basis constitutes a
treatment technique violation of 310 CMR 22.20A(3)(b)1. The Department must
be notified within 24 hours of the failure to provide Disinfection as required.
2. The Residual Disinfectant Concentration in the water entering the Distribution
System, measured as specified in 310 CMR 22.20A(5)(a)2. and (c)2., cannot be less
than 0.2 mg/l for more than four hours.
3. The Residual Disinfectant Concentration in the Distribution System, measured as
free chlorine, total chlorine, combined chlorine, or chlorine dioxide, as specified in
310 CMR 22.20A(5)(a)2. and (c)3., cannot be undetectable in more than 5% of the
samples each month, for any two consecutive months that the system serves water to the
public. Water in the Distribution System with a heterotrophic bacteria concentration
less than or equal to 500/ml, measured as heterotrophic plate count (HPC) as specified
in 310 CMR 22.20A(5)(a)1., is deemed to have a detectable Disinfectant residual for
purposes of determining compliance with this requirement. Thus the value "V" in the
following formula cannot exceed 5% in one month, for any two consecutive months.
22.20A: continued
Where:
a = number of instances where the Residual Disinfectant Concentration is measured;
b = number of instances where the Residual Disinfectant Concentration is not
measured but heterotrophic bacteria plate count (HPC) is measured;
c = number of instances where the Residual Disinfectant Concentration is measured
but not detected and no HPC is measured;
d = number of instances where no Residual Disinfectant Concentration is measured
but not detected and where the HPC is >500/ml; and
e = number of instances where the Residual Disinfectant Concentration is not
measured and HPC is >500/ml.
(4) Filtration. A Supplier of Water that uses a Surface Water Source or a groundwater source
under the direct influence of surface water, and does not meet all of the criteria in 310 CMR
22.20A(2)(a) and (b) for avoiding Filtration, must provide treatment consisting of both
Disinfection, as specified in 310 CMR 22.20A(3)(b), and Filtration treatment which complies
with the requirements of 310 CMR 22.20A(4) by June 29, 1993, or within 18 months of the
failure to meet any one of the criteria for avoiding Filtration in 310 CMR 22.20A(2)(a) and (b),
whichever is later. Failure to meet any requirement of 310 CMR 22.20A after the date specified
in 310 CMR 22.20A(4) is a Treatment Technique violation.
(a) Conventional Filtration Treatment or Direct Filtration.
1. Beginning January 1, 2002, systems using conventional and Direct Filtration
treatment serving at least 10,000 people shall meet the Turbidity requirements in
310 CMR 22.20D(4) and (5).
2. Beginning January 1, 2005, systems serving less than 10,000 people must meet the
Turbidity requirements in 310 CMR 22.20F(6) and (7).
(b) Slow Sand Filtration.
1. For systems using Slow Sand Filtration, the Turbidity level of representative
samples of a system's filtered water must be less than or equal to one NTU in at least
95% of the measurements taken each month, measured as specified in 310 CMR
22.20A(5)(a)1. and (c)1.
2. The Turbidity level of representative samples of a system's filtered water must at no
time exceed five NTU, measured as specified in 310 CMR 22.20A(5)(a)1. and (c)1.
(c) Diatomaceous Earth Filtration.
1. For systems using Diatomaceous Earth Filtration, the Turbidity level of
representative samples of a system's filtered water must be less than or equal to one
NTU in at least 95% of the measurements taken each month, measured as specified in
310 CMR 22.20A(5)(a)1. and (c)1.
2. The Turbidity level of representative samples of a system's filtered water must at no
time exceed five NTU, measured as specified in 310 CMR 22.20A(5)(a)1. and (c)1.
(d) Other Filtration Technologies. Each Supplier of Water may use a Filtration technology
not listed in 310 CMR 22.20A(4)(a) through (c), if it demonstrates to the Department, using
pilot plant studies or other means, that the alternative Filtration technology, in combination
with Disinfection treatment that meets the requirements of 310 CMR 22.20A(3)(b),
consistently achieves 99.9% removal and/or inactivation of Giardia lamblia cysts and
99.99% removal and/or inactivation of Viruses. For a Supplier of Water that makes this
demonstration, the requirements of 310 CMR 22.20A(3)(b) apply. Beginning
January 1, 2002, a Supplier of Water serving at least 10,000 people shall meet the
requirements for other Filtration technologies as required in 310 CMR 22.20D(4)(b).
Beginning January 1, 2005, a Supplier of Water serving fewer than 10,000 people must meet
the requirements for other Filtration technologies as required in 310 CMR 22.20F(6)(c).
22.20A: continued
(5) Analytical and Monitoring Requirements.
(a) Analytical Requirements. Only the analytical method(s) specified in 310 CMR
22.20A(5)(a), or otherwise approved by EPA, may be used to demonstrate compliance with
the requirements of 310 CMR 22.20A(2), through (4). Measurements for pH, temperature,
Turbidity, and Residual Disinfectant Concentrations must be conducted by a certified
operator. Measurements for total coliform, fecal coliform, and HPC must be conducted by
a laboratory certified by the Department to do such analyses. The following procedures
shall be performed in accordance with the publications listed in the 310 CMR 22.20A(6).
This incorporation by reference was approved by the Director of the Federal Register in
accordance with 5 U.S.C. 552(a) and 1 CFR Part 51. Copies of the methods published in
Standard Methods for the Examination of Water and Wastewater may be obtained from the
American Public Health Association, 1015 Fifteenth Street, N.W., Washington, D.C. 20005;
copies of the Minimal Medium ONPG MUG Method as set forth in the article National
Field Evaluation of a Defined Substrate Method for the Simultaneous Enumeration of Total
Coliform and Escherichia coli from Drinking Water: Comparison with the Standard
Multiple Tube Fermentation Method (Edberg et al.), Applied and Environmental
Microbiology, Volume 54, pp.1594 1601, June 1988 (as amended under Erratum, Applied
and Environmental Microbiology, Volume 54, p. 3197, December 1988), may be obtained
from the American Water Works Association Research Foundation, 6666 West Quincy
Avenue, Denver, Colorado, 80235; and copies of the Indigo Method as set forth in the
article Determination of Ozone in Water by the Indigo Method (Bader and Hoigne), may be
obtained from Ozone Science & Engineering, Pergamon Press Ltd., Fairview Park,
Elmsford, New York 10523. Copies may be inspected at the U.S. Environmental Protection
Agency, Room EB15, 401 M Street, S.W., Washington, D.C. 20460 or at the Office of the
Federal Register, 800 North Capitol Street, NW., suite 700 Washington, D.C.
1. Public Water Systems must conduct analysis of pH and temperature in accordance
with one of the methods listed in 310 CMR 22.06B(10). Public Water Systems must
conduct analysis of total coliforms, fecal coliforms, Heterotrophic bacteria, and
Turbidity in accordance with one of the following analytical methods and by using
analytical test procedures contained in Technical Notes on Drinking Water Methods,
EPA-600/R-94-173, October 1994, which is available at NTIS PB95-104766.
Organism
Methodology
Citiation1
Total Coliform2
Fecal Coliforms2
Heterotrophic bacteria2
Turbidity13
Total Coliform Fermentation Technique3, 4, 5
Total Coliform Membrane Filter Technique6
ONPG-MUG Test7
Fecal Coliform Procedure8
Fecal Coliform Filter Procedure
Pour Plate Method
SimPlate11
Nephelometric Method
Nephelometric Method
Great Lakes Instruments
Hach Filter Trak
9221 A, B, C
9222 A, B, C
9221 E
9222 D
9215 B
2130 B
Method 210
The procedures shall be done in accordance with the documents listed below. The incorporation by
reference of the following documents listed in footnotes 1, 6, 7, 9 and 10 was approved by the Director
of the Federal Register in accordance with 5 U.S.C. 552(a) and 1 CFR part 51. Copies of the documents
may be obtained from the sources listed below. Information regarding obtaining these documents can
be obtained from the Safe Drinking Water Hotline at 800-426-4791. Documents may be inspected at
EPA's Drinking Water Docket, 1200 Pennsylvania Ave., NW., Washington, DC 20460 (Telephone:
202-260-3027); or at the Office of the Federal Register, 800 North Capitol Street, NW, Suite 700,
Washington, D.C. 20408.
22.20A: continued
Except where noted, all methods refer to Standard Methods for the Examination of Water and
Wastewater, 18 edition (1992), 19 edition (1995), or 20 edition (1998), American Public Health
th
th
th
Association, 1015 Fifteenth Street NW, Washington, D.C. 20005. The cited methods published in any
of these three editions may be used. In addition, the following online versions may also be used: 2130
B-01, 9215 B-00, 9221 A, B, C, E-99, 9222 A, B, C, D-97, and 9223 B-97. Standard Methods Online
are available at http://www.standardmethods.org. The year in which each method was approved by the
standard Methods Committee is designated by the last two digits in the method number. The methods
listed are the only Online versions that may be used.
The time from sample collection to initiation of analysis may not exceed eight hours. Systems must hold
samples below 10°C during transit.
Lactose broth, as commercially available, may be used in lieu of lauryl tryptose broth, if the system
conducts at least 25 parallel tests between this medium and lauryl tryptose broth using the water normally
tested, and this comparison demonstrates that the false-positive rate and false-negative rate for total
coliform, using lactose broth, is less than 10%.
Media should cover inverted tubes at least ½ to b after the sample is added.
No requirement exists to run the completed phase on 10% of all total coliform-positive confirmed tubes.
MI agar also may be used. Preparation and use of MI agar is set forth in the article, New Medium for the
Simultaneous Detection of Total Coliform and Escherichia Coli in Water by Brenner, K.P., et al., 1993,
Appl. Environ. Microbiol. 59:3534-3544. Also available from the Office of Water Resource Center
(RC-4100), 1200 Pennsylvania Ave., NW, Washington, DC 20460, EPA 600/J-99/225.
The ONPG-MUG Test is also known as the Autoanalysis Colilert System.
A-1 Broth may be held up to seven days in a tightly closed screw cap tube at 4°C.
Methods for the Determination of Inorganic Substances in Environmental Samples, EPA/600/R-93/100,
August 1993. Available at NTIS, PB94-121811.
GLI Method 2, Turbidity, November 2, 1992, Great Lakes Instruments, Inc., 8855 North 55 Street,
th
Milwaukee, Wisconsin 53223.
A description of the SimPlate method, IDEXX SimPlate TM HPC Test Method for Heterotrophs in Water,
November 2000, can be obtained from IDEXX Laboratories, Inc., 1 IDEXX Drive, Westbrook, ME
04092, telephone 800-321-0207.
A description of the Hach Filter Trak Method 10133, Determination of Turbidity by Laser Nephelometry,
January 2000, Revision 2.0, can be obtained from; Hach Co., P.O. Box 389, Loveland, CO 80539-0389,
telephone: 800-227-4224.
Styrene divinyl benzene beads (e.g., AMCO-AEPA-1 or equivalent) and stabilized formazin (e.g., Hach
StablCal or equivalent) are acceptable substitutes for formazin.
2. Public Water Systems must measure Residual Disinfectant Concentrations with one
of the following methods in the following table. Residual Disinfectant Concentrations
for free chlorine and combined chlorine also may be measured by using digital meter
versions of DPD colorimetric test kits. Suppliers serving less than or equal to 3,300
persons may use non-digital meter DPD colorimetric test kits. Free chlorine and total
chlorine may be measured continuously by adapting a specified chlorine residual method
for use with a continuous monitoring instrument provided the chemistry, accuracy, and
precision remain the same. Instruments used for continuous monitoring must be
calibrated with a grab sample measurement at least every five days, or with a protocol
approved by the Department. In addition, Public Water Systems may use the ITS free
chlorine test strip for the determination of free chlorine. Use of the test strips is
described in Method D99-003, Free Chlorine Species (HOCL- and OCL-) by Test Strip,
Revision 3.0, November 21, 2003, available from Industrial Test Systems, Inc., 1875
Langston St., Rock Hill, SC 29730.
22.20A: continued
Residual
Methodology
Methods SM
SM Online
Other
Free Chlorine
Total Chlorine
Chlorine Dioxide
Ozone
Amperometric Titration
DPD Ferrous Titrimetric
DPD Colorimetric
Syringaldazine (FACTS)
Amperometric Titration
Amperometric Titration
(low level measurement)
DPD Ferrous Titrimetric
DPD Colorimetric
Iodometric Electrode
Amperometric Titration
DPD Method
Amperometric Titration
Spectrophotometric
Indigo Method
4500-Cl D
4500-Cl F
4500-Cl G
4500-Cl H
4500-Cl D
4500-Cl E
4500-Cl F
4500-Cl G
4500-Cl I
4500-ClO C
4500-ClO D
4500-ClO E
4500-O B
4500-C1 D-00
4500-C1 F-00
4500-C1 G-00
4500 C1 H-00
4500 C1 D-00
4500 C1 E-00
4500 C1 F-00
4500 C1 G-00
4500 C1 I-00
4500-ClO2 C-00
4500 C1O2
E-00
4500-O3 B-97
D 1253-033
D 1253-033
327.0, Revision 1.14
All the listed Disinfectant residual methods are contained in the 18 , 19 , and 20 editions of Standard
th
th
th
Methods for the Examination of Water and Wastewater, 1992, 1995, and 1998; the cited methods
published in any of these three editions may be used.
Standard Methods Online are available at
http:/www.standardmethods.org. The year in which each
method was approved by the Standard Methods Committee is designated by the last two digits in the
method number. The methods listed are the only Online versions that may be used.
Annual Book of ASTM Standards, Vol. 11.01, 2004; ASTM International; any year containing the cited
version of the method may be used. Copies of this method may be obtained from ASTM International,
100 Barr Harbor Drive, P.O. Box C700 West Conshohocken, PA 19428-2959.
EPA Method 327.0, Revision 1.1, Determination of chlorine Dioxide and Chlorite Ion in Drinking Water
Using Lissamine Green B and Horseradish Peroxidase with Detection by Visible Spectrophotometry,
USEPA, May 2005, EPA 815-R-05-008.
Available online at http://www.epa.gov/safewater/methods/sourcalt.html.
(b) Monitoring Requirements for Systems that Do Not Provide Filtration. A Supplier of
Water that uses a Surface Water Source and does not provide Filtration treatment must begin
monitoring, as specified in 310 CMR 22.20A(5)(b) beginning May 1, 1990, unless the
Department has notified it in writing that Filtration is required, in which case the Department
may specify alternative monitoring requirements, as appropriate, until Filtration is in place.
A Supplier of Water that uses a groundwater source under the direct influence of surface
water and does not provide Filtration treatment must begin monitoring as specified in
310 CMR 22.20A(5)(b) beginning December 31, 1990 or six months after the Department
determines that the groundwater source is under the direct influence of surface water,
whichever is later, unless the Department has notified it in writing that Filtration is required,
in which case the Department may specify alternative monitoring requirements, as
appropriate, until Filtration is in place.
1. Fecal coliform or total coliform density measurements as required by 310 CMR
22.20A(2)(a)1. must be performed on representative source water samples immediately
prior to the first or only Point of Disinfectant Application. The Supplier of Water must
sample for fecal or total coliform at the following minimum frequency each week the
system serves water to the public:
22.20A: continued
System Size (Persons Served)
Samples/Week1
< 500
501- 3,300
3,301-10,000
10,001-25,000
> 25,000
Must be taken on separate days.
In addition, one fecal or total coliform density measurement must be made every day
the system serves water to the public and the Turbidity of the source water exceeds one
NTU (these samples count towards the weekly coliform sampling requirement) unless
the Department determines that the Supplier of Water for logistical reasons outside of the
supplier's control, cannot have the sample analyzed within 30 hours of collection.
2. Turbidity measurements as required by 310 CMR 22.20A(2)(a)2. must be performed
on representative grab samples of source water immediately prior to the first or only
Point of Disinfectant Application every four hours (or more frequently) that the system
serves water to the public. A Supplier of Water may substitute continuous Turbidity
monitoring for grab sample monitoring if it validates the continuous measurement for
accuracy on a regular basis using a protocol approved by the Department.
3. The total inactivation ratio for each day that the system is in operation must be
determined based on the CT99.9 values in 310 CMR 22.20A(5)(b)3.: Tables 1.1 through
1.6, Table 2.1 and Table 3.1. The parameters necessary to determine the total
inactivation ratio must be monitored as follows:
a. The temperature of the disinfected water must be measured at least once per day
at each Residual Disinfectant Concentration Sampling Point.
b. If the system uses chlorine, the pH of the disinfected water must be measured at
least once per day at each chlorine Residual Disinfectant Concentration Sampling
Point.
c. The Disinfectant Contact Time(s) ("T") must be determined for each day during
peak hourly flow.
d. The Residual Disinfectant Concentration(s) ("C") of the water before or at the
first customer must be measured each day during peak hourly flow.
e. If a system uses a Disinfectant other than chlorine, the system may demonstrate
to the Department, through the use of a Department approved protocol for on site
Disinfection challenge studies or other information satisfactory to the Department,
that CT99.9 values other than those specified in 310 CMR 22.20A(5)(b)3.: Table 2.1
and Table 3.1 in are adequate to demonstrate that the system is achieving the
minimum inactivation rates required by 310 CMR 22.20A(3)(a)1.
TABLE 1.1 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF
GIARDIA LAMBLIA CYSTS BY FREE CHLORINE AT 0.5°C OR LOWER*
Free
pH
Residual
(mg/l)
< 6.0
< 9.0
<
22.20A: continued
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature and at the higher pH.
TABLE 1.2 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF GIARDIA
LAMBLIA CYSTS BY FREE CHLORINE AT 5.0°C*
pH
Free
Residual
(mg/l)
< 6.0
< 9.0
<
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature, and at the higher pH. If no interpolation is used, use the CT99.9 value at the
lower temperature, and at the higher pH.
TABLE 1.3 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF GIARDIA
LAMBLIA CYSTS BY FREE CHLORINE AT 10°C*
pH
Free
Residual
(mg/l)
< 6.0
< 9.0
<
22.20A: continued
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature, and at the higher pH.
TABLE 1.4 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF GIARDIA
LAMBLIA CYSTS BY FREE CHLORINE AT 15°C*
pH
Free
Residual
(mg/l)
< 6.0
< 9.0
<
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature, and at the higher pH.
TABLE 1.5 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF GIARDIA
LAMBLIA CYSTS BY FREE CHLORINE AT 20°C*
pH
Free
Residual
(mg/l)
< 6.0
< 9.0
<
22.20A: continued
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature, and at the higher pH.
TABLE 1.6 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF GIARDIA
LAMBLIA CYSTS BY FREE CHLORINE AT 25°C AND HIGHER
*
pH
Free
Residual
(mg/l)
< 6.0
< 9.0
<
These CT values achieve greater than a 99.99% inactivation of Viruses. CT values between the indicated
*
pH values may be determined by linear interpolation. CT values between the indicated temperatures of
different tables may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature, and at the higher pH.
TABLE 2.1 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION OF
GIARDIA LAMBLIA CYSTS BY CHLORINE DIOXIDE AND OZONE*
Temperature
< 1°C
5°C
10°C
15°C
20°C
> 25°C
Chlorine dioxide
Ozone
These CT values achieve greater than 99.99% inactivation of Viruses. CT values between the indicated
*
temperatures may be determined by linear interpolation. If no interpolation is used, use the CT
value
at the lower temperature for determining CT
values between indicated temperatures.
TABLE 3.1 - 310 CMR 22.20A
CT VALUES (CT
) FOR 99.9% INACTIVATION
OF GIARDIA LAMBLIA CYSTS BY CHLORAMINE*
Temperature
< 1°C
5°C
10°C
15°C
20°C
> 25°C
3,800
2,200
1,850
1,500
1,100
22.20A: continued
These values are for pH values of 6 through 9. These CT values may be assumed to achieve greater than
*
99.99% inactivation of Viruses only if chlorine is added and mixed in the water prior to the addition of
ammonia. If this condition is not met, the system must demonstrate, based on on-site studies or other
information, as approved by the State, that the system is achieving at least 99.99% inactivation of Viruses.
CT values between the indicated temperatures may be determined by linear interpolation. If no
interpolation is used, use the CT
value at the lower temperature for determining CT
values between
indicated temperatures.
4. The total inactivation ratio must be calculated as follows:
a. If the system uses only one Point of Disinfectant Application, the Supplier of
Water may determine the total inactivation ratio based on either of the following two
methods:
i. One inactivation ratio (CTcalc/CT
) is determined before or at the first
customer during peak hourly flow and if the CTcalc/CT
> 1.0, the 99.9%
Giardia lamblia inactivation requirement has been achieved; or
ii. Successive CTcalc/CT
values, representing sequential inactivation ratios,
are determined between the Point of Disinfectant Application and a point before
or at the first customer during peak hourly flow. Under this alternative, the
following method must be used to calculate the total inactivation ratio:
A. Determine
for each sequence.
B. A
dd the values together
C. If , then the
99.9% Giardia lamblia inactivation
requirement has been achieved.
b. If the system uses more than one Point of Disinfectant Application before or at
the first customer, the Supplier of Water must determine the CT value of each
Disinfection sequence immediately prior to the next Point of Disinfectant Application
during peak hourly flow. The CTcalc/CT
value of each sequence and
must be calculated using the method in 310 CMR 22.20A(5)(b)4.a.ii. to determine
if the Supplier of Water is in compliance with 310 CMR 22.20A(3)(a).
c. Although not required, the total percent inactivation for a system with one or
more points of Residual Disinfectant Concentration following equation:
22.20A: continued
5. The Residual Disinfectant Concentration of the water entering the Distribution
System must be monitored continuously, and the lowest value must be recorded each day,
except that if there is a failure in the continuous monitoring equipment, grab sampling
every four hours may be conducted in lieu of continuous monitoring, but for no more
than five working days following the failure of the equipment. Systems serving 3,300
or fewer persons may take grab samples in lieu of providing continuous monitoring on
an ongoing basis at the frequencies prescribed below:
System size by population
Samples/day*
< 500
501-1,000
1,001-2,500
2,501-3,300
The day's samples cannot be taken at the same time. The sampling intervals are subject to Department
*
review and approval.
If at any time the Residual Disinfectant Concentration falls below 0.2 mg/l in a
system using grab sampling in lieu of continuous monitoring, the Supplier of Water must
take a grab sample every four hours until the Residual Disinfectant Concentration is
equal to or greater than 0.2 mg/l.
6. The Residual Disinfectant Concentration must be measured at least at the same points
in the Distribution System and at the same time as total coliform are sampled, as
specified in 310 CMR 22.05, except that the Department may allow a Supplier of Water
which uses both a Surface Water Source or a groundwater source under direct influence
of surface water, and a groundwater source, to take Disinfectant residual samples at
points other than the total coliform Sampling Points if the Department determines that
such points are more representative of treated (disinfected) water quality within the
Distribution System. Heterotrophic bacteria, measured as heterotrophic plate count
(HPC) as specified in 310 CMR 22.20A(5)(a)1., may be measured in lieu of Residual
Disinfectant Concentration.
(c) Monitoring Requirements for Systems Using Filtration Treatment. A Supplier of Water
that uses a Surface Water Source or a groundwater source under the influence of surface
water and provides Filtration treatment must monitor in accordance with 310 CMR
22.20A(5)(c) beginning June 29, 1993, or when Filtration is installed, whichever is later.
1. Turbidity measurements as required by 310 CMR 22.20A(4) must be performed on
representative samples of the system's filtered water every four hours (or more
frequently) that the system serves water to the public. A Supplier of Water may
substitute continuous Turbidity monitoring for grab sample monitoring if it validates the
continuous measurement for accuracy on a regular basis using a protocol approved by the
Department. For any systems using Slow Sand Filtration, the Department may reduce
the sampling frequency to no less than once per day if it determines that less frequent
monitoring is sufficient to indicate effective Filtration performance.
2. The Residual Disinfectant Concentration of the water entering the Distribution
System must be monitored continuously, and the lowest value must be recorded each day,
except that if there is a failure in the continuous monitoring equipment, grab sampling
every four hours may be conducted in lieu of continuous monitoring, but for no more
than five working days following the failure of the equipment. Systems serving 3,300 or
fewer persons may take grab samples in lieu of providing continuous monitoring on an
ongoing basis at the frequencies each day prescribed below:
System size by population
Samples/day*
<500
501-1,000
1,001-2,500
2,501-3,300
The day's samples cannot be taken at the same time. The sampling intervals are subject to Department
*
review and approval.
22.20A: continued
3. The Residual Disinfectant Concentration must be measured at least at the same points
in the Distribution System and at the same time as total coliform are sampled, as
specified in 310 CMR 22.05, except that the Department may allow a Supplier of Water
which uses both a Surface Water Source or a groundwater source under direct influence
of surface water, and a groundwater source to take Disinfectant residual samples at points
other than the total coliform Sampling Points if the Department determines that such
points are more representative of treated (disinfected) water quality within the
Distribution System. Heterotrophic bacteria, measured as heterotrophic plate count
(HPC) as specified in 310 CMR 22.20A(5)(a)1., may be measured in lieu of Residual
Disinfectant Concentration.
(6) Reporting and Recordkeeping Requirements.
(a) A Supplier of Water that uses a Surface Water Source and does not provide Filtration
treatment must report monthly to the Department the information specified in 310 CMR
22.20A(6)(a) beginning May 1, 1990, unless the Department has notified the Supplier of
Water in writing that Filtration is required in writing, in which case the Department may
specify alternative reporting requirements, as appropriate, until Filtration is in place. A
Supplier of Water that uses a groundwater source under the direct influence of surface water
and does not provide Filtration treatment must report monthly to the Department the
information specified in 310 CMR 22.20A(6)(a) beginning December 31, 1990 or six months
after the Department determines that the groundwater source is under the direct influence of
surface water, whichever is later, unless the Department has notified it in writing that
Filtration is required in which case the Department may specify alternative reporting
requirements, as appropriate, until Filtration is in place.
1. Source water quality information must be reported to the Department within ten days
after the end of each month the system serves water to the public. Information that must
be reported includes:
a. The cumulative number of months for which results are reported.
b. The number of fecal and/or total coliform samples, whichever are analyzed
during the month (if a system monitors for both, only fecal coliform must be
reported), the dates of sample collection, and the dates when the Turbidity level
exceeded one NTU.
c. The number of samples during the month that had equal to or less than 20/100 ml
fecal coliform and/or equal to or less than 100/100 ml total coliform, whichever are
analyzed.
d. The cumulative number of fecal or total coliform samples, whichever are
analyzed, during the previous six months the system served water to the public.
e. The cumulative number of samples that had equal to or less than 20/100 ml fecal
coliform or equal to or less than 100/100 ml total coliform, whichever are analyzed,
during the previous six months the system served water to the public.
f. The percentage of samples that had equal to or less than 20/100 ml fecal coliform
or equal to or less than 100/100 ml total coliform, whichever are analyzed, during the
previous six months the system served water to the public.
g. The maximum Turbidity level measured during the month, the date(s) of
occurrence for any measurement(s) which exceeded five NTU, and the date(s) the
occurrence(s) was reported to the Department.
h. For the first 12 months of recordkeeping, the dates and cumulative number of
events during which the Turbidity exceeded five NTU, and after one year of
recordkeeping for Turbidity measurements, the dates and cumulative number of
events during which the Turbidity exceeded five NTU in the previous 12 months the
system served water to the public.
i. For the first 120 months of recordkeeping, the dates and cumulative number of
events during which the Turbidity exceeded five NTU, and after ten years of
recordkeeping for Turbidity measurements, the dates and cumulative number of
events during which the Turbidity exceeded five NTU in the previous 120 months the
system served water to the public.
2. Disinfection information specified in 310 CMR 22.20A(5)(b) must be reported to the
Department within ten days after the end of each month the system serves water to the
public. Information that must be reported includes:
22.20A: continued
a. For each day, the lowest measurement of Residual Disinfectant Concentration in
mg/l in water entering the Distribution System.
b. The date and duration of each period when the Residual Disinfectant
Concentration in water entering the Distribution System fell below 0.2 mg/l and
when the Department was notified of the occurrence.
c. The daily Residual Disinfectant Concentration(s) (in mg/l) and Disinfectant
Contact Time(s) (in minutes) used for calculating the CT value(s).
d. If chlorine is used, the daily measurement(s) of pH of disinfected water following
each point of chlorine Disinfection.
e. The daily measurement(s) of water temperature in C following each point of
Disinfection.
f. The daily CTcalc and CTcalc/CT
values for each Disinfectant measurement or
sequence and the sum of all CTcalc/CT
values ((CTcalc/CT
)) before or at the
first customer.
g. The daily determination of whether Disinfection achieves adequate Giardia cyst
and Virus inactivation, i.e., whether (CTcalc/CT
) is at least 1.0 or, where
Disinfectants other than chlorine are used, other indicator conditions that the
Department determines are appropriate, are met.
h. The following information on the samples taken in the Distribution System in
conjunction with total coliform monitoring pursuant to 310 CMR 22.20A(3):
i. Number of instances where the Residual Disinfectant Concentration is
measured;
ii. Number of instances where the Residual Disinfectant Concentration is not
measured but heterotrophic bacteria plate count (HPC) is measured;
iii Number of instances where the Residual Disinfectant Concentration is
measured but not detected and no HPC is measured;
iv. Number of instances where the Residual Disinfectant Concentration is
measured but not detected and where HPC is >500/ml;
v. Number of instances where the Residual Disinfectant Concentration is not
measured and HPC is >500/ml;
vi. For the current and previous month the system served water to the public, the
value of "V" in the following formula:
Where
a = the value in 310 CMR 22.20A(6)(a)2.h.i.
b = the value in 310 CMR 22.20A(6)(a)2.h.ii.
c = the value in 310 CMR 22.20A(6)(a)2.h.iii.
d = the value in 310 CMR 22.20A(6)(a)2.h.iv.
e = the value in 310 CMR 22.20A(6)(a)2.h.v.
i. A system need not report the data listed in 310 CMR 22.20A(6)(a)2.a., and c.
through f., if all data listed in 310 CMR 22.20A(6)(a)2.a. through f. remains on file
at the system, and the Department determines that:
i. The Supplier of Water has submitted to the Department all the information
required by 310 CMR 22.20A(6)(a)2.a. through h. for at least 12 months; and
ii. The Department has determined that the system is not required to provide
Filtration treatment.
3. No later than January 10 of each year, each Supplier of Water must provide to the
th
Department a report which summarizes its compliance with all watershed control
program requirements specified in 310 CMR 22.20A(2)(b)5.
4. No later than January 10 of each year each system must provide to the Department
th
a report on the on site inspection conducted during that year pursuant to 310 CMR
22.20A(2)(b)6. unless the on site inspection was conducted by the Department.
5. Each Supplier of Water, upon discovering that a Waterborne Disease Outbreak
potentially attributable to its water system has occurred, must report that occurrence to
the Department as soon as possible, but no later than by the end of the next business day.
22.20A: continued
6. If at any time the Turbidity exceeds five NTU, the Supplier of Water must consult
with the Department as soon as practical, but not later than 24 hours after the exceedance
is known, in accordance with the public notification requirements under 310 CMR
22.16(3)(b)3.
7. If at any time the residual falls below 0.2 mg/l in the water entering the Distribution
System, the Supplier of Water must notify the Department as soon as possible, but no
later than by the end of the next business day. The Supplier of Water also must notify
the Department by the end of the next business day whether or not the residual was
restored to at least 0.2 mg/l within four hours.
(b) A Supplier of Water that uses a Surface Water Source or a groundwater source under
the direct influence of surface water and provides Filtration treatment must report monthly
to the Department the information specified in 310 CMR 22.20A(6)(b) beginning
June 29, 1993, or when Filtration is installed, whichever is later.
1. Turbidity measurements as required by 310 CMR 22.20A(5)(c)1. must be reported
within ten days after the end of each month the system serves water to the public.
Information that must be reported includes:
a. The total number of filtered water Turbidity measurements taken during the
month.
b. The number and percentage of filtered water Turbidity measurements taken
during the month which are less than or equal to the Turbidity limits specified in
310 CMR 22.20A(4) for the Filtration technology being used.
c. The date and value of any Turbidity measurements taken during the month which
exceed five NTU.
2. Disinfection information specified in 310 CMR 22.20A(5)(c) must be reported to the
Department within ten days after the end of each month the system serves water to the
public. Information that must be reported includes:
a. For each day, the lowest measurement of Residual Disinfectant Concentration in
mg/l in water entering the Distribution System.
b. The date and duration of each period when the Residual Disinfectant
Concentration in water entering the Distribution System fell below 0.2 mg/l and
when the Department was notified of the occurrence.
c. The following information on the samples taken in the Distribution System in
conjunction with total coliform monitoring pursuant to 310 CMR 22.20A(3):
i. Number of instances where the Residual Disinfectant Concentration is
measured;
ii. Number of instances where the Residual Disinfectant Concentration is not
measured but heterotrophic bacteria plate count (HPC) is measured;
iii. Number of instances where the Residual Disinfectant Concentration is
measured but not detected and no HPC is measured;
iv. Number of instances where Residual Disinfectant Concentration is measured
but not detected and where HPC is >500/ml;
v. Number of instances where the Residual Disinfectant Concentration is not
measured and HPC is >500/ml;
vi. For the current and previous month the system serves water to the public, the
value of "V" in the following formula:
Where
a = the value in 310 CMR 22.20A(6)(b)2.c.i.
b = the value in 310 CMR 22.20A(6)(b)2.c.ii.
c = the value in 310 CMR 22.20A(6)(b)2.c.iii.
d = the value in 310 CMR 22.20A(6)(b)2.c.iv.
e = the value in 310 CMR 22.20A(6)(b)2.c.v.
d. A Supplier of Water need not report the data listed in 310 CMR 22.20A(6)(b)2.a.
if all data listed in 310 CMR 22.20A(6)(b)2.a. through c. remains on file at the
system and the Department determines that the system has submitted all the
information required by 310 CMR 22.20A(6)(b)2.a. through c. for at least 12 months.
22.20A: continued
3. A Supplier of Water, upon discovering that a Waterborne Disease Outbreak
potentially attributable to its water system has occurred, must report that occurrence to
the Department as soon as possible, but no later than by the end of the next business day.
4. If at any time the Turbidity exceeds five NTU, the Supplier of Water must consult
with the Department as soon as practical, but not later than 24 hours after the exceedance
is known, in accordance with the public notification requirements under 310 CMR
22.16(3)(b)3.
5. If at any time the residual falls below 0.2 mg/l in the water entering the Distribution
System, the Supplier of Water must notify the Department as soon as possible, but no
later than by the end of the next business day. The system also must notify the
Department by the end of the next business day whether or not the residual was restored
to at least 0.2 mg/l within four hours.
(7) Review of Filtration Determinations.
(a) The Department's determination whether a Supplier of Water must provide Filtration
will be made in writing based on the criteria set forth in 310 CMR 22.20A(2). The Supplier
of Water shall publish a copy of the Department's determination in a newspaper of general
circulation in the area served by the Supplier of Water within ten days of receipt of the same.
The determination will include a statement that the Supplier of Water and Persons served by
the system may request a hearing in accordance with 310 CMR 22.20A(7)(b). Within ten
days of publication, the Supplier of Water shall submit an affidavit to the Department
attesting to the fact that the determination has been published.
(b) The Supplier of Water, and any Person served by the system, may request review of the
determination at a public hearing by submitting a written request to the Regional Director at
the Department's Regional Office that serves the area where the Public Water System at issue
is located within 15 days of the date of publication.
(c) Following receipt of a request for a public hearing, the Department will give notice of
the hearing by mail to the Supplier of Water and, if the request was made by a Person other
than the Supplier of Water, to the Person who submitted the request. The Supplier of Water
shall publish a copy of the notice of hearing in a newspaper of general circulation in the area
served by the system within ten days of receipt of the same. Within ten days of publication,
the Supplier of Water shall submit an affidavit to the Department attesting to the fact that the
notice has been published.
(d) The Department will accept written comments from the public relevant to the
determination up to at least 14 days following the hearing. A determination following the
hearing that a Supplier of Water must provide Filtration will not be subject to further review;
a determination that a Supplier of Water meets all of the criteria for avoiding Filtration will
be subject to the Department's on going review. In the event the Department finds that a
Supplier of Water no longer meets any one of the criteria for avoiding Filtration, the
Department will issue a determination in writing that will be subject to review at a public
hearing in accordance with 310 CMR 22.20A(7).