310 CMR 22.20G
Table 1.
310 CMR 22.20G: Table 1
SOURCE WATER MONITORING STARTING DATES
Systems that serve:
Must begin the first round of
source water monitoring no
later than the month
beginning:
And must begin the second
round of source water
monitoring no later than the
month beginning:
At least 100,000 people
October 1, 2006
April 1, 2015
From 50,000 to 99,999 people
April 1, 2007
October 1, 2015
From 10,000 to 49,999 people
April 1, 2008
October 1, 2016
Fewer than 10,000 and monitor
for E. coli1
October 1, 2008
October 1, 2017
Fewer than 10,000 and monitor
for Cryptosporidium2
April 1, 2010
April 1, 2019
Applies only to filtered systems.
Applies to filtered systems that meet the conditions of 310 CMR 22.20G(2)(a)4. and unfiltered systems.
(d) Monitoring Avoidance.
1. Filtered systems are not required to conduct source water monitoring under 310 CMR
22.20G if the system will provide a total of at least 5.5-log of treatment for
Cryptosporidium, equivalent to meeting the treatment requirements of Bin 4 in 310 CMR
22.20G(12).
2. Unfiltered systems are not required to conduct source water monitoring under
310 CMR 22.20G if the system will provide a total of at least 3-log Cryptosporidium
inactivation, equivalent to meeting the treatment requirements for unfiltered systems with
a mean Cryptosporidium concentration of greater than 0.01 oocysts/L in 310 CMR
22.20G(13).
22.20G: continued
3. If a system chooses to provide the level of treatment in 310 CMR 22.20G(2)(d)1. or
2., as applicable, rather than start source water monitoring, the system must notify the
Department in writing no later than the date the system is otherwise required to submit
a sampling schedule for monitoring under 310 CMR 22.20G(3). Alternatively, a system
may choose to stop sampling at any point after it has initiated monitoring if it notifies the
Department in writing that it will provide this level of treatment. Systems must install
and operate technologies to provide this level of treatment by the applicable treatment
compliance date in 310 CMR 22.20G(14).
(e) Plants Operating Only Part of the Year. Suppliers of water with plants served by a
Surface Water Source or groundwater source under the direct influence of surface water that
operate for only part of the year must conduct source water monitoring in accordance with
310 CMR 22.20G, but with the following modifications:
1. Systems must sample their source water only during the months that the plant
operates unless the Department specifies another monitoring period based on plant
operating practices.
2. Systems with plants that operate less than six months per year and that monitor for
Cryptosporidium must collect at least six Cryptosporidium samples per year during each
of two years of monitoring. Samples must be evenly spaced throughout the period the
plant operates.
(f) 1. New Sources. A system that begins using a New Source of Surface Water or
groundwater under the direct influence of surface water after the system is required to
begin monitoring under 310 CMR 22.20G(2)(c) must monitor the New Source on a
schedule the Department approves. Source water monitoring must meet the requirements
of 310 CMR 22.20G. The system must also meet the bin classification and
Cryptosporidium treatment requirements of 310 CMR 22.20G(11) and (12) or (13), as
applicable, for the New Source on a schedule the Department approves.
2. The requirements of 310 CMR 22.20G(2)(f) apply to suppliers of water with a
Surface Water Source or groundwater source under the direct influence of surface water
that begin operation after the monitoring start date applicable to the system’s size under
310 CMR 22.20G(2)(c).
3. The system must begin a second round of source water monitoring no later than six
years following initial bin classification under 310 CMR 22.20G(11) or determination
of the mean Cryptosporidium level under 310 CMR 22.20G(13), as applicable.
(g) Failure to collect any source water sample required under 310 CMR 22.20G(2) in
accordance with the sampling schedule, sampling location, analytical method, approved
laboratory, and reporting requirements of 310 CMR 22.20G(3) through (7) is a monitoring
violation.
(h) Grandfathering Monitoring Data. Systems may use (grandfather) monitoring data
collected prior to the applicable monitoring start date in 310 CMR 22.20G(2)(c) to meet the
initial source water monitoring requirements in 310 CMR 22.20G(a). Grandfathered data
may substitute for an equivalent number of months at the end of the monitoring period. All
data submitted under 310 CMR 22.20G(2)(h) must meet the requirements in 310 CMR
22.20G(8).
(3) Sampling Schedules.
(a) Systems required to conduct source water monitoring under 310 CMR 22.20G(2) must
submit a sampling schedule that specifies the calendar dates when the system will collect
each required sample.
1. Systems must submit sampling schedules no later than three months prior to the
applicable date listed in 310 CMR 22.20G(2)(c) for each round of required monitoring.
2. a. Systems serving at least 10,000 people must submit their sampling schedule for
the initial round of source water monitoring under 310 CMR 22.20G(2)(a) to EPA
electronically at https://intranet.epa.gov/lt2/.
b. If a system is unable to submit the sampling schedule electronically, the system
may use an alternative approach for submitting the sampling schedule that EPA or
the Department approves.
22.20G: continued
3. Systems serving fewer than 10,000 people must submit their sampling schedules for
the initial round of source water monitoring 310 CMR 22.20G(2)(a) to the Department.
4. Systems must submit sampling schedules for the second round of source water
monitoring 310 CMR 22.20G(2)(b) to the Department.
5. If the Department does not respond to a system regarding its sampling schedule, the
system must sample at the reported schedule.
(b) Systems must collect samples within two days before or two days after the dates
indicated in their sampling schedule (i.e., within a five-day period around the schedule date)
unless one of the conditions of 310 CMR 22.20G(3)(b)1. or 2. applies.
1. If an extreme condition or situation exists that may pose danger to the sample
collector, or that cannot be avoided and causes the system to be unable to sample in the
scheduled five-day period, the system must sample as close to the scheduled date as is
feasible unless the Department approves an alternative sampling date. The system must
submit an explanation for the delayed sampling date to the Department concurrent with
the shipment of the sample to the laboratory.
2. a. If a system is unable to report a valid analytical result for a scheduled sampling
date due to equipment failure, loss of or damage to the sample, failure to comply with
the analytical method requirements, including the quality control requirements in
310 CMR 22.20G(5), or the failure of an approved laboratory to analyze the sample,
then the system must collect a replacement sample.
b. The system must collect the replacement sample not later than 21 days after
receiving information that an analytical result cannot be reported for the scheduled
date unless the system demonstrates that collecting a replacement sample within this
time frame is not feasible or the Department approves an alternative resampling date.
The system must submit an explanation for the delayed sampling date to the
Department concurrent with the shipment of the sample to the laboratory.
(c) Systems that fail to meet the criteria of 310 CMR 22.20G(3)(b) for any source water
sample required under 310 CMR 22.20G(2) must revise their sampling schedules to add
dates for collecting all missed samples. Systems must submit the revised schedule to the
Department for approval prior to when the system begins collecting the missed samples.
(4) Sampling Locations.
(a) Systems required to conduct source water monitoring under 310 CMR 22.20G(2) must
collect samples for each plant that treats a Surface Water Source, or a groundwater source
under the direct influence of surface water. Where multiple plants draw water from the same
influent, such as the same pipe or intake, the Department may approve one set of monitoring
results to be used to satisfy the requirements of 310 CMR 22.20G(2) for all plants.
(b) 1. Systems must collect source water samples prior to chemical treatment, such as
coagulants, oxidants and disinfectants, unless the system meets the condition specified
in 310 CMR 22.20G(4)(b)2.
2. The Department may approve a system to collect a source water sample after
chemical treatment. To grant this approval, the Department will determine that
collecting a sample prior to chemical treatment is not feasible for the system and that the
chemical treatment is unlikely to have a significant adverse effect on the analysis of the
sample.
(c) Systems that recycle filter backwash water must collect source water samples prior to
the point of filter backwash water addition.
(d) Bank Filtration.
1. Systems that receive Cryptosporidium treatment credit for Bank Filtration under
310 CMR 22.20D(4)(b) or 22.20F(6)(c), as applicable, must collect source water samples
in the Surface Water prior to Bank Filtration.
2. Systems that use Bank Filtration as pretreatment to a Filtration plant must collect
source water samples from the well (i.e., after Bank Filtration). Use of Bank Filtration
during monitoring must be consistent with routine operational practice. Systems
collecting samples after a Bank Filtration process may not receive treatment credit for the
bank filtration under the Massachusetts Drinking Water Guidelines and Policies,
Appendix N, Requirements for Microbial Toolbox Options for Meeting Cryptosporidium
Treatment Requirements under the Long Term 2 Enhanced Surface Water Treatment
Rule for Public Water Systems.
22.20G: continued
(e) Multiple Sources. Systems with plants that use multiple water sources, including
multiple Surface Water Sources and blended Surface Water and groundwater sources, must
collect samples as specified in 310 CMR 22.20G(4)(e)1. or 2. The use of multiple sources
during monitoring must be consistent with routine operational practice.
1. If a sampling tap is available where the sources are combined prior to treatment,
systems must collect samples from the tap.
2. If a sampling tap where the sources are combined prior to treatment is not available,
systems must collect samples at each source near the intake on the same day and must
follow either 310 CMR 22.20G(4)(e)2.a. or b. for sample analysis.
a. Systems may composite samples from each source into one sample prior to
analysis. The volume of sample from each source must be weighted according to the
proportion of the source in the total plant flow at the time the sample is collected.
b. Systems may analyze samples from each source separately and calculate a
weighted average of the analysis results for each sampling date. The weighted
average must be calculated by multiplying the analysis result for each source by the
fraction the source contributed to total plant flow at the time the sample was collected
and then summing these values.
(f) Additional Requirements. Systems must submit a description of their sampling
location(s) to the Department at the same time as the sampling schedule required under
310 CMR 22.20G(3). This description must address the position of the sampling location
in relation to the system’s water source(s) and treatment processes, including pretreatment,
points of chemical treatment, and filter backwash recycle. If the Department does not
respond to a system regarding sampling location(s), the system must sample at the reported
location(s).
(5) Analytical Methods.
(a) Cryptosporidium. Systems must analyze for Cryptosporidium using Method 1623:
Cryptosporidium and Giardia in Water by Filtration/IMS/FA, 2005, United States
Environmental Protection Agency, EPA–815-R–05–002 or Method 1622: Cryptosporidium
in Water by Filtration/IMS/FA, 2005, United States Environmental Protection Agency,
EPA–815–R–05–001, which are incorporated by reference.
1. Systems must analyze at least a 10 L sample or a packed pellet volume of at least 2
mL as generated by the methods listed in 310 CMR 22.20G(5)(a). Systems unable to
process a 10 L sample must analyze as much sample volume as can be filtered by two
filters approved by EPA and the Department for the methods listed in 310 CMR
22.20G(5)(a), up to a packed pellet volume of at least 2 mL.
2. Matrix spike (MS) samples, as required by the methods in 310 CMR 22.20G(5)(a),
must be spiked and filtered by a laboratory approved for Cryptosporidium analysis under
310 CMR 22.20G(6). If the volume of the MS sample is greater than 10 L, the system
may filter all but 10 L of the MS sample in the field, and ship the filtered sample and the
remaining 10 L of source water to the laboratory. In this case, the laboratory must spike
the remaining 10 L of water and filter it through the filter used to collect the balance of
the sample in the field.
3. Flow cytometer-counted spiking suspensions must be used for MS samples and
ongoing precision and recovery (OPR) samples.
(b) E. coli. Systems must use methods for enumeration of E. coli in source water approved
in accordance with 310 CMR 22.26(3)(c).
1. The time from sample collection to initiation of analysis may not exceed 30 hours
unless the system meets the condition of 310 CMR 22.20G(5)(b)2.
2. The Department may approve on a case-by-case basis the holding of an E. coli
sample for up to 48 hours between sample collection and initiation of analysis if the
Department determines that analyzing an E. coli sample within 30 hours is not feasible.
E. coli samples held between 30 to 48 hours must be analyzed by the Colilert reagent
version of Standard Method 9223B as listed in 310 CMR 22.26(3)(c).
3. Systems must maintain samples between 0/C and 10/C during storage and transit to
the laboratory.
(c) Turbidity. Systems must use methods for Turbidity measurement approved in 310 CMR
22.20A(5)(a)1.
22.20G: continued
(6) Approved Laboratories.
(a) Cryptosporidium. Systems must have Cryptosporidium samples analyzed by a
laboratory that is approved under EPA’s Laboratory Quality Assurance Evaluation Program
for Analysis of Cryptosporidium in Water or a laboratory that has been certified for
Cryptosporidium analysis by an equivalent Department laboratory certification program.
(b) E. coli. Any laboratory certified by the EPA, the National Environmental Laboratory
Accreditation Conference or the Department for total coliform or fecal coliform analysis
under 310 CMR 22.20A(5) is approved for E. coli analysis under 310 CMR 22.20G when
the laboratory uses the same technique for E. coli that the laboratory uses for 310 CMR
22.20A(5).
(c) Turbidity. Measurements of Turbidity must be made by a party approved by the
Department.
(7) Reporting Source Water Monitoring Results.
(a) Systems must report results from the source water monitoring required under 310 CMR
22.20G(2) no later than ten days after the end of the first month following the month when
the sample is collected.
(b) All systems serving at least 10,000 people must report the results from the initial source
water monitoring required under 310 CMR 22.20G(2)(a) to EPA electronically at https://
intranet.epa.gov/lt2/. If a system is unable to report monitoring results electronically, the
system may use an alternative approach for reporting monitoring results that EPA approves.
(c) Systems serving fewer than 10,000 individuals must report results from the initial source
water monitoring required under 310 CMR 22.20G(2)(a) to the Department.
(d) All systems must report results from the second round of source water monitoring
required under 310 CMR 22.20G(2)(b) to the Department.
(e) Systems must report the applicable information in paragraphs 310 CMR 22.20G(7)(e)1.
and 2. for the source water monitoring required under 310 CMR 22.20G(2).
1. Systems must report the following data elements for each Cryptosporidium analysis:
a. PWS ID;
b. Facility ID;
c. Sample collection date;
d. Sample type (field or matrix spike);
e. Sample volume filtered (L), to nearest ¼ L;
f. Was 100% of filtered volume examined; and
g. Number of oocysts counted.
i. For matrix spike samples, systems must also report the sample volume spiked
and estimated number of oocysts spiked. These data are not required for field
samples.
ii. For samples in which less than 10 L is filtered or less than 100% of the
sample volume is examined, systems must also report the number of filters used
and the packed pellet volume.
ii. For samples in which less than 100% of sample volume is examined, systems
must also report the volume of resuspended concentrate and volume of this
resuspension processed through immunomagnetic separation.
2. Systems must report the following data elements for each E. coli analysis:
a. PWS ID;
b. Facility ID;
c. Sample collection date;
d. Analytical method number;
e. Method type;
f. Source type (flowing stream, Lake/Reservoir, GWUDI);
g. E. coli/100 mL; and
h. Turbidity.1
Systems serving fewer than 10,000 individuals that are not required to monitor for Turbidity as specified
in 310 CMR 22.20G(2) are not required to report Turbidity with their E. coli results.
22.20G: continued
(8) Grandfathering Previously Collected Data.
(a) 1. Systems may comply with the initial source water monitoring requirements of
310 CMR 22.20G(2)(a) by grandfathering sample results collected before the system is
required to begin monitoring (i.e., previously collected data). To be grandfathered, the
sample results and analysis must meet the criteria in 310 CMR 22.20G(8) and the
Department must approve.
2. A filtered system may grandfather Cryptosporidium samples to meet the requirements
of 310 CMR 22.20G(2)(a) when the system does not have corresponding E. coli and
Turbidity samples. A system that grandfathers Cryptosporidium samples without E. coli
and Turbidity samples is not required to collect E. coli and Turbidity samples when the
system completes the requirements for Cryptosporidium monitoring under 310 CMR
22.20G(2)(a).
(b) E. coli Sample Analysis. The analysis of E. coli samples must meet the analytical
method and approved laboratory requirements of 310 CMR 22.20G(5) through (6).
(c) Cryptosporidium Sample Analysis. The analysis of Cryptosporidium samples must
meet the criteria in 310 CMR 22.20G(8)(c).
1. Laboratories analyzed Cryptosporidium samples using one of the analytical methods
in 310 CMR 22.20G(8)(c)1.a. through f., which are incorporated by reference.
a. Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA,
2005, United States Environmental Protection Agency, EPA–815–R–05–002.
b. Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 2005, United
States Environmental Protection Agency, EPA–815–R–05–001.
c. Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA,
2001, United States Environmental Protection Agency, EPA–821–R–01–025.
d. Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 2001, United
States Environmental Protection Agency, EPA–821–-R–01–026.
e. Method 1623: Cryptosporidium and Giardia in Water by Filtration/IMS/ FA,
1999, United States Environmental Protection Agency, EPA–82 1–R–99–006.
f. Method 1622: Cryptosporidium in Water by Filtration/IMS/FA, 1999, United
Departments Environmental Protection Agency, EPA–821–R–99–001.
2. For each Cryptosporidium sample, the laboratory analyzed at least 10 L of sample or
at least 2 mL of packed pellet or as much volume as could be filtered by two filters that
EPA and the Department approved for the methods listed in 310 CMR 22.20G(8)(c)1.
(d) Sampling Location. The sampling location must meet the conditions as specified in
310 CMR 22.20G(4).
(e) Sampling Frequency. Cryptosporidium samples were collected no less frequently than
each calendar month on a regular schedule, beginning no earlier than January 1999. Sample
collection intervals may vary for the conditions specified in 310 CMR 22.20G(3)(b)1. and
2. if the system provides documentation of the condition when reporting monitoring results.
1. The Department may approve grandfathering of previously collected data where there
are time gaps in the sampling frequency if the system conducts additional monitoring the
Department specifies to ensure that the data used to comply with the initial source water
monitoring requirements of 310 CMR 22.20G(2)(a) are seasonally representative and
unbiased.
2. Systems may grandfather previously collected data where the sampling frequency
within each month varied. If the Cryptosporidium sampling frequency varied, systems
must follow the monthly averaging procedure in 310 CMR 22.20G(11)(b)5. or 310 CMR
22.20G(13)(a)3., as applicable, when calculating the bin classification for filtered
systems or the mean Cryptosporidium concentration for unfiltered systems.
(f) Reporting Monitoring Results for Grandfathering. Systems that request to grandfather
previously collected monitoring results must report the following information by the
applicable dates listed in 310 CMR 22.20G(3).
1. Systems must report that they intend to submit previously collected monitoring
results for grandfathering. This report must specify the number of previously collected
results the system will submit, the dates of the first and last sample, and whether a system
will conduct additional source water monitoring to meet the requirements of 310 CMR
22.20G(2)(a). Systems must report this information no later than the date required by the
sampling schedule under 310 CMR 22.20G(3).
22.20G: continued
2. Systems must report previously collected monitoring results for grandfathering, along
with the associated documentation listed in 310 CMR 22.20G(8)(f)(2)a. through d., no
later than two months after the applicable date listed in 310 CMR 22.20G(2)(c).
a. For each sample result, systems must report the applicable data elements in
310 CMR 22.20G(7).
b. Systems must certify that the reported monitoring results include all results the
system generated during the time period beginning with the first reported result and
ending with the final reported result. This applies to samples that were collected
from the sampling location specified for source water monitoring under 310 CMR
22.20G, not spiked, and analyzed using the laboratory’s routine process for the
analytical methods listed in 310 CMR 22.20G.
c. Systems must certify that the samples were representative of a plant’s source
water(s) and the source water(s) have not changed. Systems must report a description
of the sampling location(s), which must address the position of the sampling location
in relation to the system’s water source(s) and treatment processes, including points
of chemical addition and filter backwash recycle.
d. For Cryptosporidium samples, the laboratory or laboratories that analyzed the
samples must provide a letter certifying that the quality control criteria specified in
the methods listed in 310 CMR 22.20G(8)(c)1. were met for each sample batch
associated with the reported results. Alternatively, the laboratory may provide bench
sheets and sample examination report forms for each field, matrix spike, IPR, OPR,
and method blank sample associated with the reported results.
(g) If the Department determines that a previously collected data set submitted for
grandfathering was generated during source water conditions that were not normal for the
system, such as a drought, the Department may disapprove the data. Alternatively, the
Department may approve the previously collected data if the system reports additional source
water monitoring data, as determined by the Department, to ensure that the data set used
under 310 CMR 22.20G(11) or (13) represents average source water conditions for the
system.
(h) If a system submits previously collected data that fully meet the number of samples
required for initial source water monitoring under 310 CMR 22.20G(2)(a) and some of the
data are rejected due to not meeting the requirements of 310 CMR 22.20G(8), systems must
conduct additional monitoring to replace rejected data on a schedule the Department
approves. Systems are not required to begin this additional monitoring until two months
after notification that data have been rejected and additional monitoring is necessary.
(9) Requirements When Making a Significant Change in Disinfection Practice.
(a) Following the completion of initial source water monitoring under 310 CMR
22.20G(2)(a), a system that plans to make a significant change to its Disinfection practice,
as defined in 310 CMR 22.20G(9)(b), must develop Disinfection Profiles and calculate
Disinfection benchmarks for Giardia lamblia and Viruses as described in 310 CMR
22.20G(10). Prior to changing the Disinfection practice, the system must notify the
Department and must include in this notice the information in 310 CMR 22.20G(9)(a)1.
through 3.
1. A completed Disinfection Profile and Disinfection benchmark for Giardia lamblia
and Viruses as described in 310 CMR 22.20G(10).
2. A description of the proposed change in Disinfection practice.
3. An analysis of how the proposed change will affect the current level of Disinfection.
(b) Significant changes to Disinfection practice are defined as follows:
1. Changes to the point of Disinfection;
2. Changes to the Disinfectant(s) used in the treatment plant;
3. Changes to the Disinfection process; or
4. Any other modification identified by the Department as a significant change to
Disinfection practice.
22.20G: continued
(10) Developing the Disinfection Profile and Benchmark.
(a) Systems required to develop Disinfection Profiles under 310 CMR 22.20G(9) must
follow the requirements of 310 CMR 22.20G(10). Systems must monitor at least weekly for
a period of 12 consecutive months to determine the total log inactivation for Giardia lamblia
and Viruses. If systems monitor more frequently, the monitoring frequency must be evenly
spaced. Systems that operate for fewer than 12 months per year must monitor weekly during
the period of operation. Systems must determine log inactivation for Giardia lamblia
through the entire plant, based on CT99.9 values in 310 CMR 22.20A(5)(b): Tables 1.1
through 1.6, 2.1, and 3.1 as applicable. Systems must determine log inactivation for Viruses
through the entire treatment plant based on a protocol approved by the Department.
(b) Systems with a single Point of Disinfectant Application prior to the entrance to the
Distribution System must conduct the monitoring in 310 CMR 22.20G(10)(b)1. through 4.
Systems with more than one Point of Disinfectant Application must conduct the monitoring
in 310 CMR 22.20G(10)(b)1. through 4. for each Disinfection segment. Systems must
monitor the parameters necessary to determine the total inactivation ratio, using analytical
methods in 310 CMR 22.20A(5)(a).
1. For systems using a Disinfectant other than UV, the temperature of the disinfected
water must be measured at each Residual Disinfectant Concentration Sampling Point
during peak hourly flow or at an alternative location approved by the Department.
2. For systems using chlorine, the pH of the disinfected water must be measured at each
chlorine Residual Disinfectant Concentration Sampling Point during peak hourly flow
or at an alternative location approved by the Department.
3. The Disinfectant Contact Time(s) (t) must be determined during peak hourly flow.
4. The Residual Disinfectant Concentration(s) (C) of the water before or at the first
customer and prior to each additional Point of Disinfectant Application must be
measured during peak hourly flow.
(c) In lieu of conducting new monitoring under 310 CMR 22.20G(10)(b), systems may elect
to meet the requirements of 310 CMR 22.20G(10)(c)1. or 2.
1. Systems that have at least one year of existing data that are substantially equivalent
to data collected under the provisions of 310 CMR 22.20G(10)(b) may use these data to
develop Disinfection Profiles as specified in 310 CMR 22.20G(10) if the system has
neither made a significant change to its treatment practice nor changed sources since the
data were collected. Systems may develop Disinfection Profiles using up to three years
of existing data.
2. Systems may use Disinfection Profile(s) developed under 310 CMR 22.20D(3) or (4)
in lieu of developing a new profile if the system has neither made a significant change
to its treatment practice nor changed sources since the profile was developed. Systems
that have not developed a Virus profile under 310 CMR 22.20D(3) or 22.20F(4) must
develop a Virus profile using the same monitoring data on which the Giardia lamblia
profile is based.
(d) Systems must calculate the total inactivation ratio for Giardia lamblia as specified in
310 CMR 22.20G(10)(d)1. through 3.
1. Systems using only one Point of Disinfectant Application may determine the total
inactivation ratio for the Disinfection segment based on either of the methods in
310 CMR 22.2G(10)(d)1.a. or b.
a. Determine one inactivation ratio (CTcalc/CT
) before or at the first customer
during peak hourly flow.
b. Determine successive CTcalc/ CT
values, representing sequential inactivation
ratios, between the Point of Disinfectant Application and a point before or at the first
customer during peak hourly flow. The system must calculate the total inactivation
ratio by determining (CTcalc/CT
) for each sequence and then adding the (CTcalc/
CT
) values together to determine (G (CTcalc/CT
)).
2. Systems using more than one Point of Disinfectant Application before the first
customer must determine the CT value of each Disinfection segment immediately prior
to the next Point of Disinfectant Application, or for the final segment, before or at the
first customer, during peak hourly flow. The (CTcalc/ CT
) value of each segment and
((CTcalc/CT
)) must be calculated using the method in 310 CMR 22.20G(10)(d)1.b.
22.20G: continued
3. The system must determine the total logs of inactivation by multiplying the value
calculated in 310 CMR 22.20G(10)(d)1. or 2. by 3.0.
4. Systems must calculate the log of inactivation for Viruses using a protocol approved
by the Department.
(e) Systems must use the procedures specified in 310 CMR 22.20G(10)(e)1. and 2. to
calculate a Disinfection benchmark.
1. For each year of profiling data collected and calculated under 310 CMR
22.20G(10)(a) through (d), systems must determine the lowest mean monthly level of
both Giardia lamblia and Virus inactivation. Systems must determine the mean Giardia
lamblia and Virus inactivation for each calendar month for each year of profiling data by
dividing the sum of daily or weekly Giardia lamblia and Virus log inactivation by the
number of values calculated for that month.
2. The Disinfection benchmark is the lowest monthly mean value (for systems with one
year of profiling data) or the mean of the lowest monthly mean values (for systems with
more than one year of profiling data) of Giardia lamblia and Virus log inactivation in
each year of profiling data.
(11) Bin Classification for Filtered Systems.
(a) Following completion of the initial round of source water monitoring required under
310 CMR 22.20G(2)(a), filtered systems must calculate an initial Cryptosporidium bin
concentration for each plant for which monitoring was required. Calculation of the bin
concentration must use the Cryptosporidium results reported under 310 CMR 22.20G(2)(a)
and must follow the procedures in 310 CMR 22.20G(11)(b)1. through 5.
(b) 1. For systems that collect a total of at least 48 samples, the bin concentration is equal
to the arithmetic mean of all sample concentrations.
2. For systems that collect a total of at least 24 samples, but not more than 47 samples,
the bin concentration is equal to the highest arithmetic mean of all sample concentrations
in any 12 consecutive months during which Cryptosporidium samples were collected.
3. For systems that serve fewer than 10,000 people and monitor for Cryptosporidium
for only one year (i.e., collect 24 samples in 12 months), the bin concentration is equal
to the arithmetic mean of all sample concentrations.
4. For systems with plants operating only part of the year that monitor fewer than 12
months per year under 310 CMR 22.20G(2)(e) the bin concentration is equal to the
highest arithmetic mean of all sample concentrations during any year of Cryptosporidium
monitoring.
5. If the monthly Cryptosporidium sampling frequency varies, systems must first
calculate a monthly average for each month of monitoring. Systems must then use these
monthly average concentrations, rather than individual sample concentrations, in the
applicable calculation for bin classification in 310 CMR 22.20G(11)(b)1. through 4.
(c) Filtered systems must determine their initial bin classification from 310 CMR 22.20G:
Table 2 and using the Cryptosporidium bin concentration calculated under 310 CMR
22.20G(11)(a) and (b):
22.20G: continued
310 CMR 22.20G: Table 2
BIN CLASSIFICATION TABLE FOR FILTERED SYSTEMS
For Systems that are:
With a Cryptosporidium bin
concentration of …1
The bin classification is…
Required to monitor for
Cryptosporidium under
310 CMR 22.20G (2)
Cryptosporidium <0.075
oocysts/L
Bin 1
0.075 oocysts/L<Cryptosporidium
<1.0 oocysts/L
Bin 2
1.0 oocysts/L< Cryptosporidium
<3.0 oocysts/L
Bin 3
Cryptosporidium >3.0 oocysts/L
Bin 4
Serving fewer than 10,000
people and NOT required to
monitor for Cryptosporidium
under 310 CMR 22.20G(2)(a)4.
N/A
Bin 1
Based on calculations in 310 CMR 22.20G(11)(a) or (d), as applicable.
(d) Following completion of the second round of source water monitoring required under
310 CMR 22.20G(2)(b) filtered systems must recalculate their Cryptosporidium bin
concentration using the Cryptosporidium results reported under 310 CMR 22.20G(7)(d) and
following the procedures in 310 CMR 22.20G(11)(b)1. through 4. Systems must then
redetermine their bin classification using this bin concentration and the table in 310 CMR
22.20G(11)(c).
(e) 1. Filtered systems must report their initial bin classification under 310 CMR
22.20G(11)(c) to the Department for approval no later than six months after the system
is required to complete initial source water monitoring based on the schedule in
310 CMR 22.20G(2)(c).
2. Systems must report their bin classification under 310 CMR 22.20G(11)(d) to the
Department for approval no later than six months after the system is required to complete
the second round of source water monitoring based on the schedule in 310 CMR
22.20G(2)(c).
3. The bin classification report to the Department must include a summary of source
water monitoring data and the calculation procedure used to determine bin classification.
(f) Failure to comply with the conditions of 310 CMR 22.20G(11)(e) is a violation of the
Treatment Technique requirement.
(12) Filtered System Additional Cryptosporidium Treatment Requirements.
(a) Filtered systems must provide the level of additional treatment for Cryptosporidium
specified in 310 CMR 22.20G(12)(a) based on their bin classification as determined under
310 CMR 22.20G(11) and according to the schedule in 310 CMR 22.20G(14).
22.20G: continued
310 CMR 22.20G: Table 3
FILTERED SYSTEM ADDITIONAL CRYPTOSPORIDIUM TREATMENT REQUIREMENTS
If the system bin
classification is …
And the system uses the following Filtration treatment in full compliance with 310 CMR
22.20A, 310 CMR 22.20D, and 310 CMR 22.20F (as applicable), then the additional
Cryptosporidium treatment requirements are …
Conventional
Filtration treatment
(including softening) Direct Filtration
Slow Sand or
Diatomaceous Earth
Filtration
Alternative Filtration
technologies
Bin 1
No additional
treatment
No additional
treatment
No additional
treatment
No additional treatment
Bin 2
1-log treatment
1.5-log treatment
1-log treatment
-1
Bin 3
2-log treatment
2.5-log treatment
2-log treatment
-2
Bin 4
2.5-log treatment
3-log treatment
2.5-log treatment
-3
As determined by the Department such that the total Cryptosporidium removal and inactivation is at least
4.0-log.
As determined by the Department such that the total Cryptosporidium removal and inactivation is at least
5.0-log.
As determined by the Department such that the total Cryptosporidium removal and inactivation is at least
5.5-log.
(b) 1. Filtered systems must use one or more of the treatment and management options
listed in 310 CMR 22.20G(18) to comply with the additional Cryptosporidium treatment
required in 310 CMR 22.20G(12)(a).
2. Systems classified in Bin 3 and Bin 4 must achieve at least 1-log of the additional
Cryptosporidium treatment required under 310 CMR 22.20G(12)(a) using either one or
a combination of the following: Bag Filters, Bank Filtration, Cartridge Filters, chlorine
dioxide, membranes, ozone, or UV, in accordance with 310 CMR 22.20G(19) through
(23).
(c) Failure by a system in any month to achieve treatment credit by meeting criteria in
310 CMR 22.20G(19) through (23), that is at least equal to the level of treatment required
in 310 CMR 22.20G(12)(a) is a violation of the Treatment Technique requirement.
(d) If the Department determines during a Sanitary Survey or an equivalent source water
assessment that after a system completed the monitoring conducted under 310 CMR
22.20G(2)(a) or (b), significant changes occurred in the system's Watershed that could lead
to increased contamination of the source water by Cryptosporidium, the system must take
actions specified by the Department to address the contamination. These actions may include
additional source water monitoring and/or implementing microbial toolbox options in
accordance with 310 CMR 22.20G(18) through (23).
(13) Unfiltered System Cryptosporidium Treatment Requirements.
(a) Determination of Mean Cryptosporidium Level.
1. Following completion of the initial source water monitoring required under
310 CMR 22.20G(2)(a) unfiltered systems must calculate the arithmetic mean of all
Cryptosporidium sample concentrations reported under 310 CMR 22.20G(2)(a). Systems
must report this value to the Department for approval no later than six months after the
month the system is required to complete initial source water monitoring based on the
schedule in 310 CMR 22.20G(2)(c).
2. Following completion of the second round of source water monitoring required under
310 CMR 22.20G(2)(b) unfiltered systems must calculate the arithmetic mean of all
Cryptosporidium sample concentrations reported under 310 CMR 22.20G(2)(b).
Systems must report this value to the Department for approval no later than six months
after the month the system is required to complete the second round of source water
monitoring based on the schedule in 310 CMR 22.20G(2)(c).
22.20G: continued
3. If the monthly Cryptosporidium sampling frequency varies, systems must first
calculate a monthly average for each month of monitoring. Systems must then use these
monthly average concentrations, rather than individual sample concentrations, in the
calculation of the mean Cryptosporidium level in 310 CMR 22.20G(13)(a)1. or 2.
4. The report to the Department of the mean Cryptosporidium levels calculated under
310 CMR 22.20G(13)(a)1. and 2. must include a summary of the source water
monitoring data used for the calculation.
5. Failure to comply with the conditions of 310 CMR 22.20G(13)(a) is a violation of
the Treatment Technique requirement.
(b) Cryptosporidium Inactivation Requirements. Unfiltered systems must provide the level
of inactivation for Cryptosporidium specified in 310 CMR 22.20G(13)(b)1. and 2., based on
their mean Cryptosporidium levels as determined under 310 CMR 22.20G(13)(a) and
according to the schedule in 310 CMR 22.20G(14).
1. Unfiltered systems with a mean Cryptosporidium level of 0.01 oocysts/L or less must
provide at least 2-log Cryptosporidium inactivation.
2. Unfiltered systems with a mean Cryptosporidium level of greater than 0.01 oocysts/L
must provide at least 3-log Cryptosporidium inactivation.
(c) Inactivation Treatment Technology Requirements. Unfiltered systems must use chlorine
dioxide, ozone, or UV; in accordance with 310 CMR 22.20G(23); in order to meet the
Cryptosporidium inactivation requirements of 310 CMR 22.20G(13).
1. Systems that use chlorine dioxide or ozone and fail to achieve the Cryptosporidium
inactivation required in 310 CMR 22.20G(13)(b) on more than one day in the calendar
month are in violation of the Treatment Technique requirement.
2. Systems that use UV light, and fail to achieve the Cryptosporidium inactivation
required in 310 CMR 22.20G(13)(b) by meeting the criteria in 310 CMR
22.20G(23)(b)1.d., are in violation of the Treatment Technique requirement.
(d) Use of Two Disinfectants. Unfiltered systems must meet the combined
Cryptosporidium inactivation requirements of 310 CMR 22.20G(13) and Giardia lamblia
and Virus inactivation requirements of 310 CMR 22.20A(3)(a) using a minimum of two
Disinfectants, and each of two Disinfectants must separately achieve the total inactivation
required for Cryptosporidium, Giardia lamblia, or Viruses.
(14) Schedule for Compliance with Cryptosporidium Treatment Requirements.
(a) Following initial bin classification under 310 CMR 22.20G(11)(c), filtered systems must
provide the level of treatment for Cryptosporidium required under 310 CMR 22.20G(12)
according to the schedule in 310 CMR 22.20G(14)(c).
(b) Following initial determination of the mean Cryptosporidium level under 310 CMR
22.20G(13)(a)1., unfiltered systems must provide the level of treatment for Cryptosporidium
required under 310 CMR 22.20G(13) according to the schedule in 310 CMR 22.20G(14)(c).
(c) Cryptosporidium Treatment Compliance Dates.
310 CMR 22.20G: Table 4
Cryptosporidium TREATMENT COMPLIANCE DATES TABLE
Systems that serve …
Must comply with Cryptosporidium treatment
requirements no later than…*
(1) At least 100,000 individuals
April 1, 2012
(2) From 50,000 to 99,999 individuals
October 1, 2012
(3) From 10,000 to 49,999 individuals
October 1, 2013
(4) Fewer than 10,000 individuals
October 1, 2014
* The Department may allow up to an additional two years for complying with the treatment requirement for
systems making capital improvements.
(d) If the bin classification for a filtered system changes following the second round of
source water monitoring, as determined under 310 CMR 22.20G(11)(d), the system must
provide the level of treatment for Cryptosporidium required under 310 CMR 22.20G(12) on
a schedule the Department approves.
22.20G: continued
(e) If the mean Cryptosporidium level for an unfiltered system changes following the
second round of monitoring, as determined under 310 CMR 22.20G(13)(a)2. and if the
system must provide a different level of Cryptosporidium treatment under 310 CMR
22.20G(13) due to this change, the system must meet this treatment requirement on a
schedule the Department approves.
(15) Requirements for Uncovered Finished Water Storage Facilities.
(a) Systems using uncovered finished water storage facilities must comply with the
conditions of 310 CMR 22.20G(15).
(b) Systems must notify the Department of the use of each Uncovered Finished Water
Storage Facility no later than April 1, 2008.
(c) Systems must meet the conditions of 310 CMR 22.20G(15)(c)1. or 2. for each
Uncovered Finished Water Storage Facility or be in compliance with a Department-approved
schedule to meet these conditions no later than April 1, 2009.
1. Systems must cover any Uncovered Finished Water Storage Facility.
2. Systems must treat the discharge from the Uncovered Finished Water Storage
Facility to the Distribution System to achieve inactivation and/or removal of at least
4-log Virus, 3-log Giardia lamblia, and 2-log Cryptosporidium using a protocol
approved by the Department.
(d) Failure to comply with the requirements of 310 CMR 22.20G(15) is a violation of the
Treatment Technique requirement.
(16) Reporting Requirements.
(a) Systems must report sampling schedules under 310 CMR 22.20G(3) and source water
monitoring results under 310 CMR 22.20G(7) unless they notify the Department that they
will not conduct source water monitoring due to meeting the criteria of 310 CMR
22.20G(2)(d).
(b) Systems must report the use of uncovered finished water storage facilities to the
Department as described in 310 CMR 22.20G(15).
(c) Filtered systems must report their Cryptosporidium bin classification as described in
310 CMR 22.20G(11).
(d) Unfiltered systems must report their mean source water Cryptosporidium level as
described in 310 CMR 22.20G(13).
(e) Systems must report Disinfection Profiles and benchmarks to the Department as
described in 310 CMR 22.20G(9) through (10) prior to making a significant change in
disinfection practice.
(f) Systems must report to the Department in accordance with the following table for any
microbial toolbox options used to comply with treatment requirements under 310 CMR
22.20G(12) or (13). Alternatively, the Department may approve a system to certify operation
within required parameters for treatment credit rather than reporting monthly operational data
for toolbox options.
310 CMR 22.20G: Table 5
MICROBIAL TOOLBOX REPORTING REQUIREMENTS
Toolbox option
Systems must submit the following information
On the following schedule
(1) Watershed
control program.
(i) Notice of intention to develop a new or
continue an existing watershed control
program…
(ii) Watershed control plan…
(iii) Annual watershed control program status
report……
(iv) Watershed sanitary survey
report……………………
No later than two years before the applicable
treatment compliance date in 310 CMR 22.20G(14).
No later than one year before the applicable
treatment compliance date in 310 CMR 22.20G(14).
Every 12 months, beginning one year after the
applicable treatment compliance date in 310 CMR
22.20G(14).
For Community Water Systems, every three years
beginning three years after the applicable treatment
compliance date in 310 CMR 22.20G(14). For
Noncommunity Water Systems, every five years
beginning five years after the applicable treatment
compliance date in 310 CMR 22.20G(14).
22.20G: continued
Toolbox option
Systems must submit the following information
On the following schedule
(2) Alternative
source/intake
management
Verification that system has relocated the intake
or adopted the intake withdrawal procedure
reflected in monitoring results.
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
(3) Pre-sediments
Monthly verification of the following:
(i) Continuous basin operation
(ii) Treatment of 100% of the flow
(iii) Continuous addition of a coagulant
(iv) At least 0.5-log mean reduction of influent
Turbidity or compliance with alternative
Department approved performance criteria.
Monthly reporting within ten days following the
month in which the monitoring was conducted
beginning on the applicable treatment compliance
date in 310 CMR 22.20G(14).
(4) Two-stage
Lime Softening
Monthly verification of the following:
(i) Chemical addition and hardness
precipitation occurred in two separate and
sequential softening stages prior to Filtration
(ii) Both stages treated 100% of the plant
flow.
Monthly reporting within ten days following the
month in which the monitoring was conducted
beginning on the applicable treatment compliance
date in 310 CMR 22.20G(14).
(5) Bank Filtration
(i) Initial demonstration of the following:
(A) Unconsolidated, predominantly sandy
aquifer
(B) Setback distance of at least 25 ft.
(0.5-log credit) or 50 ft. (1.0-log credit).
(ii) If monthly average of daily max Turbidity
is greater than one NTU then system must
report result and submit an assessment of the
cause.
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
Report within 30 days following the month in which
the monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(6) Combined filter
performance
Monthly verification of combined filter effluent
(CFE) Turbidity levels less than or equal to
0.15 NTU in at least 95% of the four hour CFE
measurements taken each month.
Monthly reporting within ten days following the
month in which the monitoring was conducted,
beginning on the applicable treatment compliance
date in 310 CMR 22.20G(14).
(7) Individual filter
performance
Monthly verification of the following:
(i) Individual filter effluent (IFE) Turbidity
levels less than or equal to 0.15 NTU in at least
95% of samples each month in each filter.
(ii) No individual filter greater than 0.3 NTU
in two consecutive readings 15 minutes apart.
Monthly reporting within ten days following the
month in which the monitoring was conducted,
beginning on the applicable treatment compliance
date in 310 CMR 22.20G(14).
(8) Demonstration
of performance
(i) Results from testing following a
Department-approved protocol.
(ii) As required by the Department, monthly
verification of operation within conditions of
Department approval for demonstration of
performance credit.
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(9) Bag Filters and
Cartridge Filters
(i) Demonstration that the following criteria
are met:
(A) Process meets the definition of bag or
cartridge Filtration;
(B) Removal efficiency established through
challenge testing that meets criteria in
310 CMR 22.20G(22)(a).
(ii) Monthly verification that 100% of plant
flow was filtered.
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(10) Membrane
Filtration
(i) Results of verification testing
demonstrating the following:
(A) Removal efficiency established through
challenge testing that meets criteria in
310 CMR 22.20G(22)(b).
(B) Integrity test method and parameters,
including resolution, sensitivity, test
frequency, control limits, and
associated baseline.
(ii) Monthly report summarizing the
following:
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
22.20G: continued
Toolbox option
Systems must submit the following information
On the following schedule
(A) All direct integrity tests above the
control limit;
(B) If applicable, any Turbidity or
alternative Department approved indirect
integrity monitoring results triggering direct
integrity testing and the corrective action that
was taken.
(11) Second stage
Filtration
Monthly verification that 100% of flow was
filtered through both stages and that first stage
was preceded by Coagulation step.
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(12) Slow Sand
Filtration (as
secondary filter)
Monthly verification that both a slow sand filter
and a preceding separate stage of Filtration
treated 100% of flow from Surface Water
Sources or Groundwater Under the Direct
Influence of Surface Water.
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(13) Chlorine
dioxide
Summary of CT values for each day as
described in 310 CMR 22.20G(23), as
applicable.
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(14) Ozone
Summary of CT values for each day as
described in 310 CMR 22.20G(23), as
applicable.
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(15) UV
(i) Validation test results demonstrating
operating conditions that achieve required UV
dose.
(ii) Monthly report summarizing the
percentage of water entering the Distribution
System that was not treated by UV reactors
operating within validated conditions for the
required dose as specified in 310 CMR
22.20G(23), as applicable.
No later than the applicable treatment compliance
date in 310 CMR 22.20G(14).
Within ten days following the month in which
monitoring was conducted, beginning on the
applicable treatment compliance date in 310 CMR
22.20G(14).
(17) Recordkeeping Requirements.
(a) Systems must keep results from the initial round of source water monitoring under
310 CMR 22.20G(2)(a) and the second round of source water monitoring under 310 CMR
22.20G(2)(b) until three years after bin classification under 310 CMR 22.20G(11) for filtered
systems or determination of the mean Cryptosporidium level under 310 CMR 22.20G(11)
for unfiltered systems for the particular round of monitoring.
(b) Systems must keep any notification to the Department that they will not conduct source
water monitoring due to meeting the criteria of 310 CMR 22.20G(2)(d) for three years.
(c) Systems must keep the results of treatment monitoring associated with microbial toolbox
options under 310 CMR 22.20G(18) through (23) and with uncovered finished water
reservoirs under 310 CMR 22.20G(15), as applicable, for three years.
22.20G: continued
(18) Microbial Toolbox Options for Meeting Cryptosporidium Treatment Requirements.
(a) A Public Water System may receive the Cryptosporidium treatment credits listed in
310 CMR22.20G(18)(b) Table 6, by meeting the conditions for microbial toolbox options
described in 310 CMR 22.20G(19) through (23), provided however that unfiltered systems
shall only be eligible for Cryptosporidium treatment credits for the microbial toolbox options
described in 310 CMR 22.20G(23). A Supplier of Water may apply these Cryptosporidium
treatment credits to meet the treatment requirements set forth in 310 CMR 22.20G(12) and
(13), as applicable.
(b) The following table summarizes options in the microbial toolbox set forth in 310 CMR
22.20G(19) through (23). In the event of conflict between this table and the provisions of
310 CMR 22.20G(19) through (23), the latter shall control.
310 CMR 22.20G: Table 6
MICROBIAL TOOLBOX SUMMARY TABLE: OPTIONS, TREATMENT CREDITS AND CRITERIA
Toolbox Option
Log Credit
Cryptosporidium treatment credit with
design and implementation criteria
SOURCE PROTECTION AND MANAGEMENT TOOLBOX OPTIONS
1. Watershed control program
0.5-log
For Department-approved program
comprising required elements, annual
program status report to Department, and
regular watershed survey. Unfiltered
systems are not eligible for credit. Specific
criteria are in 310 CMR 22.20G(19)(a).
2. Alternative source/intake
management
No prescribed credit
Suppliers of Water may conduct
simultaneous monitoring for treatment bin
classification at alternative intake locations
or under alternative intake management
strategies. Specific criteria are in 310 CMR
22.20G(19)(b).
PRE FILTRATION TOOLBOX OPTIONS
3. Pre-sedimentation basin with
Coagulation
0.5-log credit
Credit is given during any month that
pre-sedimentation basins achieve a monthly
mean reduction of 0.5-log or greater in
Turbidity or alternative Department-
approved performance criteria. To be
eligible, basins must be operated
continuously with coagulant addition and all
plant flow must pass through basins.
Specific criteria are in 310 CMR
22.20G(20)(a).
4. Two-stage Lime Softening
0.5-log credit
Credit for two-stage softening where
chemical addition and hardness
precipitation occur in both stages. All plant
flow must pass through both stages.
Single-stage softening is credited as
equivalent to conventional treatment.
Specific criteria are in 310 CMR
22.20G(20)(b).
22.20G: continued
Toolbox Option
Log Credit
Cryptosporidium treatment credit with
design and implementation criteria
5. Bank Filtration
0.5-log
For 25-foot setback . Specific criteria are in
310 CMR 22.20G(20)(c).
1.0-log
For 50-foot setback . Specific criteria are in
310 CMR 22.20G(20)(c).
TREATMENT PERFORMANCE TOOLBOX OPTIONS
6. Combined filter performance
0.5-log
Credit for combined filter effluent Turbidity
less than or equal to 0.15 NTU in at least 95%
of measurements each month. Specific criteria
are in 310 CMR 22.20G(21)(a).
7. Individual filter performance
0.5-log
Credit is given in addition to 0.5-log combined
filter performance credit. Credit is given if
individual filter effluent Turbidity is less than
or equal to 0.15 NTU in at least 95% of
samples each month in each filter and is never
greater than 0.3 NTU in two consecutive
measurements in any filter. Specific criteria
are in 310 CMR 22.20G(21)(b).
8. Demonstration of performance
Credit awarded
Credit awarded to unit process or treatment
train based on a demonstration to the
Department with a Department-approved
protocol. Specific criteria are in 310 CMR
22.20G(21)(c).
ADDITIONAL FILTRATION TOOLBOX OPTIONS
9. Bag or Cartridge Filters (individual
filters)
Up to 2-log
Up to 2-log credit based on the removal
efficiency demonstrated during challenge
testing with a 1.0-log factor of safety. Specific
criteria are in 310 CMR 22.20G(22)(a).
10. Bag or Cartridge Filters (in series)
Up to 2.5-log
Up to 2.5-log credit based on the removal
efficiency demonstrated during challenge
testing with a 0.5-log factor of safety. Specific
criteria are in 310 CMR 22.20G(22)(a).
11. Membrane Filtration
Log credit
Log credit equivalent to removal efficiency
demonstrated in challenge test for device if
supported by direct integrity testing. Specific
criteria are in 310 CMR 22.20G(22)(b).
12. Second stage Filtration
0.5-log
0.5-log credit for second separate granular
media Filtration stage if treatment train
includes Coagulation prior to first filter.
Specific criteria are in 310 CMR
22.20G(22)(c).
22.20G: continued
Toolbox Option
Log Credit
Cryptosporidium treatment credit with
design and implementation criteria
13. Slow sand filters
2.5-log
Credit as a secondary Filtration step .
Specific criteria are in 310 CMR
22.20G(22)(d).
3.0-log
Credit as a primary Filtration process2.
Specific criteria are in 310 CMR
22.20G(22)(d).
INACTIVATION TOOLBOX OPTIONS
14. Chlorine dioxide
CT table
Log credit based on measured CT in
relation to CT table. Specific criteria in
310 CMR 22.20G(23)(a).
15. Ozone
CT table
Log credit based on measured CT in
relation to CT table. Specific criteria in
310 CMR 22.20G(23)(a).
16. UV
UV dose
Log credit based on validated UV dose in
relation to UV dose table; reactor validation
testing required to establish UV dose and
associated operating conditions. Specific
criteria in 310 CMR 22.20G(23)(b).
Aquifer must be unconsolidated sand containing at least 10% fines; average Turbidity in wells must be less than one NTU.
Suppliers of Water using wells followed by Filtration when conducting source water monitoring must sample the well to
determine bin classification and are not eligible for additional credit.
No prior chlorination for either option.
(19) Source Toolbox Components.
(a) Watershed Control Program. Suppliers of Water may apply for a 0.5-log
Cryptosporidium treatment credit for implementing an approved watershed control program,
in accordance with the following requirements:
1. provide advance written notice to the Department of the intent to apply for the
watershed control program credit no later than two years prior to the treatment
compliance date applicable to the Public Water System in 310 CMR 22.20G(14),
Schedule for Compliance with Cryptosporidium Treatment requirements.
2. if no approved watershed control program is in place, then submit to the Department
for approval a proposed, written watershed control plan no later than one year before the
applicable treatment compliance date in 310 CMR 22.20G(14). The availability of the
watershed control program treatment credit shall be contingent on Department approval
of the watershed control plan based on the inclusion and adequacy of all of the following
elements:
a. identification of an area outside of which the likelihood of Cryptosporidium or
fecal contamination affecting the treatment Plant Intake is not significant ("area of
influence"). The area of influence shall be evaluated in future watershed surveys, as
required in 310 CMR 22.20G(19)(a)5.b.
b. identification of both potential and actual sources of Cryptosporidium
contamination and an assessment of the relative impact of these sources on the
system's source water quality.
c. an analysis of the effectiveness and feasibility of control measures that could
reduce Cryptosporidium loading from sources of contamination to the system's
source water.
d. a statement of goals and specific actions the Supplier of Water will undertake to
reduce source water Cryptosporidium levels, including:
22.20G: continued
i. an explanation of how the actions are expected to contribute to specific goals;
ii. identification of Watershed resource requirements and commitments; and
iii. a schedule for implementing the watershed control plan, once approved,
including deadlines for completing specific actions identified in the watershed
control plan.
3. if an approved watershed control program is in place as of January 5, 2006, then
submit to the Department for approval written documentation demonstrating that the
existing watershed control plan complies with the following:
a. the existing watershed control plan must meet the above criteria listed in
310 CMR 22.20G(19)(a)2. in addition to any criteria met in the existing approval;
and
b. the existing watershed control plan must specify ongoing and future actions that
will reduce source water Cryptosporidium levels.
4. Credit in the Absence of Department Response. If within 90 days of the
Department's receipt of a watershed control plan submitted under 310 CMR
22.20G(19)(a), the Department does not respond to the Supplier of Water regarding
approval of that watershed control plan, and the Supplier of Water otherwise meets the
requirements of 310 CMR 22.20G(19)(a), the watershed control plan will be considered
approved and 0.5 log Cryptosporidium treatment credit will be awarded, unless and until
the Department subsequently withdraws such approval.
5. Maintaining the 0.5-log Cryptosporidium treatment credit for implementing an
approved watershed control program. In order to maintain a 0.5-log Cryptosporidium
treatment credit for implementing an approved watershed control program, the Supplier
of Water shall satisfy the following requirements:
a. submit an annual watershed control program status report to the Department. The
annual watershed control program status report shall describe the Supplier of Water's
implementation of the approved plan and assess the adequacy of the plan to meet its
goals. It must explain how the Supplier of Water is addressing any shortcomings in
plan implementation, including those previously identified by the Department or as
the result of the watershed survey conducted under 310 CMR 22.20G(19)(a)5.b. The
Supplier of Water shall also describe any significant changes that have occurred in
the Watershed since the last watershed sanitary survey. If a Supplier of Water, based
upon implementation of an approved watershed control program, believes that a
significant change to the approved watershed control program is necessary, the
Supplier of Water shall notify the Department in writing of the changes it proposes
to make to its approved watershed control plan. Any such change to an approved
watershed control plan shall be subject to:
i. the Department's approval based upon the plan's continued inclusion of and
adequacy of the elements in 310 CMR 22.20G(19)(a)2.; and
ii. if any change is likely to reduce the level of source water protection, the
Supplier of Water's notification shall include a plan and strategy indicating how
the proposed actions will mitigate this effect.
If within 60 days of the Department's receipt of a notification of a change to an
approved watershed control plan, the Department does not respond to the Supplier
of Water regarding approval of that change, and the Supplier of Water otherwise
meets the requirements of 310 CMR 22.20G(19)(a)5.a.i. and ii., then the changes to
the approved watershed control plan will be considered approved, unless and until
the Department subsequently withdraws such approval, based upon failure to meet
such requirements.
b. undergo a watershed sanitary survey every three years for Community Water
Systems and every five years for Non-community Water Systems which:
i. encompasses the area of influence identified in the Department-approved
watershed control plan;
ii. assesses the implementation of actions to reduce source water
Cryptosporidium levels; and
iii. identifies any significant New Sources of Cryptosporidium;
22.20G: continued
iv. unless performed by the Department, is performed by a qualified Person
approved by the Department, based on demonstrated knowledge and experience
in:
A. conducting watershed inspections and reviewing and assessing impacts
to public water supplies from existing land use practices, stormwater
discharges, aquatic and terrestrial invasive species, wildlife, public access and
recreation, agriculture, local zoning and non zoning controls;
B. recommending source water protection measures to address impacts; and
C. assisting with multi-town coordination and public education for water
supply protection.
Suppliers of Water shall submit the survey report to the Department, unless the
survey is performed by the Department. If the Department determines that significant
changes have occurred in the Watershed since the previous watershed sanitary
survey, the Department may establish an earlier date than otherwise required in
310 CMR 22.20G(19)(a)5.b. by which Public Water Systems shall undergo another
watershed sanitary survey.
c. The Supplier of Water shall make the watershed control plan, annual status
reports, and watershed sanitary survey reports available to the public in electronic or
printed form, upon request. These documents shall be in plain language and include
criteria by which to evaluate the success of the program in achieving plan goals. A
Supplier of Water may request in writing the Department's written approval to
withhold from the public portions of the annual status report, watershed control plan,
and watershed sanitary survey based on water supply security considerations. Any
such request must identify with specificity the security considerations relevant to
each portion proposed to be withheld.
6. A Supplier of Water's watershed control program treatment credit shall be subject to
withdrawal if the Department determines that the Supplier of Water is not performing the
approved watershed control plan.
(b) Alternative Source.
1. A Supplier of Water may conduct source water monitoring that reflects a different
intake location (either in the same source or for an alternate source) or a different
procedure for the timing or level of withdrawal from the source (alternative source
monitoring). A Supplier of Water, subject to the Department's written approval, may
determine its bin classification under 310 CMR 22.20G(11) based on the alternative
source monitoring results.
2. If a Supplier of Water conducts alternative source monitoring under 310 CMR
22.20G(19)(b), the Supplier of Water shall also monitor its current Plant Intake
concurrently, as described in 310 CMR 22.20G(2).
3. Alternative source monitoring under 310 CMR 22.20G (19)(b)1. shall meet the
requirements for source monitoring to determine bin classification, as described in
310 CMR 22.20G(2) through (7). The Supplier of Water shall report the alternative
source monitoring results in writing to the Department, along with supporting
information documenting the operating conditions under which the samples were
collected.
4. If a Supplier of Water determines its bin classification under 310 CMR 22.20G(11)
using alternative source monitoring results that reflect a different intake location or a
different procedure for managing the timing or level of withdrawal from the source, the
Supplier of Water shall relocate the intake or permanently adopt the withdrawal
procedure, as applicable, no later than the applicable treatment compliance date in
310 CMR 22.20G(14)(c).
(20) Pre-filtration Treatment Toolbox Components.
(a) Pre-sedimentation. A Supplier of Water using Pre-sedimentation, subject to the
Department's review and written approval, shall receive a 0.5-log Cryptosporidium treatment
credit for any month the Public Water System meets the following criteria:
1. the Pre-sedimentation is in continuous operation and treats the entire plant flow taken
from a Surface Water Source or a Groundwater under the Direct Influence of Surface
Water source;
22.20G: continued
2. the Supplier of Water continuously adds a coagulant to the Pre-sedimentation basin;
and
3. the Pre-sedimentation basin achieves the following performance criteria:
a. demonstrates at least 0.5-log mean reduction of influent Turbidity. This reduction
must be determined using daily Turbidity measurements in the Pre-sedimentation
influent and effluent and must be calculated as follows: log10(monthly mean of daily
influent Turbidity) - log10(monthly mean of daily effluent Turbidity); or
b. demonstrates at least 0.5-log mean removal of micron-sized particulate material
through the Pre-sedimentation, in accordance with 310 CMR 22.20G(22)b.2.
(b) Two-stage Lime Softening. A Supplier of Water using Two-stage Lime Softening,
subject to the Department's satisfactory review and written approval, shall receive a 0.5-log
Cryptosporidium treatment credit, if chemical addition and hardness precipitation occur in
two separate and sequential softening stages prior to Filtration, and both softening stages
treat the entire plant flow taken from a Surface Water Source or a Groundwater under the
Direct Influence of Surface Water Source.
(c) Bank Filtration. A Supplier of Water using Bank Filtration that serves as pretreatment
to a Filtration plant, subject to the Department's satisfactory review and written approval of
the Bank Filtration data, shall receive Cryptosporidium treatment credit, as set forth in
310 CMR 22.20G(2)(c)1. through 8., by meeting the following criteria:
1. Suppliers of Water shall receive either 0.5-log treatment credit for wells with a
groundwater flow path of at least 25 feet or a 1.0-log treatment credit for wells with a
groundwater flow path of at least 50 feet, whichever is less. The groundwater flow path
shall be determined as specified in 310 CMR 22.20G(20)(c)4.;
2. the wells must be located in granular aquifers. Granular aquifers are comprised of
sand, clay, silt, rock fragments, pebbles or larger particles, and minor cement. A Supplier
of Water must characterize the aquifer at the well site to determine aquifer properties.
A Supplier of Water must extract a core from the aquifer and demonstrate that in at least
90% of the core length, grains less than 1.0 mm in diameter constitute at least 10% of the
core material;
3. the wells must be horizontal or vertical;
4. for vertical wells, the groundwater flow path is the measured distance from the edge
of the Surface Water body under high flow conditions (determined by the 100 year
floodplain elevation boundary or by the floodway, as defined in Federal Emergency
Management Agency flood hazard maps effective as of March 31, 2016) to the well
screen. For horizontal wells, the groundwater flow path is the measured distance from
the bed of the river under normal flow conditions to the closest horizontal well lateral
screen;
5. each wellhead must be monitored for Turbidity at least once every four hours while
the Bank Filtration is in operation and shall be subject to the following requirements:
a. if monthly average Turbidity levels, based on daily maximum values in any of the
wells being monitored, exceed one NTU, the Supplier of Water shall report this result
to the Department and conduct an assessment within 30 days to determine the cause
of the high Turbidity levels in the well; and
b. the Supplier of Water's treatment credit shall be subject to revocation if the
Department determines that microbial removal has been compromised, until such
time as the Supplier of Water implements corrective actions, as approved by the
Department, to remediate the problem;
6. Springs and Infiltration Galleries.
a. Springs and infiltration galleries shall not be eligible for a Bank Filtration
treatment credit;
b. Springs and infiltration galleries shall be eligible for credit pursuant to 310 CMR
22.20G(21)(c);
7. Bank Filtration Demonstration of Performance. A Supplier of Water, subject to the
Department's review and written approval, shall receive Cryptosporidium treatment
credit for Bank Filtration based on submittal of a demonstration of performance study
meeting the following criteria:
22.20G: continued
a. the study must follow a Department-approved protocol and must involve the
collection of data on the removal of Cryptosporidium or a surrogate for
Cryptosporidium and related hydrogeologic and water quality parameters during the
full range of operating conditions; and
b. the study must include sampling both from the production well(s) and from
monitoring wells that are screened and located along the shortest flow path between
the Surface Water Source and the production well(s).
Treatment credit based on a performance study may be greater than 1.0-log and may
be awarded for Bank Filtration that does not meet the criteria in 310 CMR
22.20G(20)(c)1. through 5.; and
8. Suppliers of Water using Bank Filtration when they begin source water monitoring
under 310 CMR 22.20G(2)(a) shall collect samples as described in 310 CMR
22.20G(4)(d), but shall not be eligible for this credit.
(21) Treatment Performance Toolbox Components.
(a) Combined Filter Performance. A Supplier of Water using Conventional Filtration
Treatment or Direct Filtration, subject to the Department's review and written approval, shall
receive a 0.5 log Cryptosporidium treatment credit during any month the combined filter
effluent (CFE) Turbidity is less than or equal to 0.15 NTU in at least 95% of the
measurements. Turbidity must be measured as described in 310 CMR 22.20A(5)(a) and (c).
Such credit shall be in addition to any other Cryptosporidium treatment credit granted to the
Public Water System pursuant to 310 CMR 22.20G.
(b) Individual Filter Performance.
1. A Supplier of Water using conventional Filtration treatment or Direct Filtration
treatment, subject to the Department's review and written approval, shall receive 0.5-log
Cryptosporidium treatment credit during any month the Public Water System meets the
following criteria:
a. the filtered water Turbidity for each individual filter must be less than or equal
to 0.15 NTU in at least 95% of the measurements recorded each month; and
b. no individual filter has a measured Turbidity greater than 0.3 NTU in two
consecutive measurements taken 15 minutes apart.
2. A Public Water System that has received Cryptosporidium treatment credit for
individual filter performance that fails to meet the requirements as specified in 310 CMR
22.20G(21)(b)1.a. or b. during any month shall not receive a Treatment Technique
violation as a result of such failure, for the month in which the failure occurred, under
310 CMR 22.20G(12)(c), if the Supplier of Water demonstrates both of the following to
the Department's satisfaction:
a. the failure was due to unusual and short-term circumstances that could not
reasonably be prevented through optimizing treatment plant design, operation and
maintenance; and
b. the Public Water System has experienced no more than two such failures in any
calendar year.
3. Compliance with these criteria shall be based on individual filter Turbidity
monitoring as described in 310 CMR 22.20A(5) or 22.20D, as applicable. Such credit
shall be in addition to any other Cryptosporidium treatment credit granted to the Public
Water System pursuant to 310 CMR 22.20G(21)(a).
(c) Demonstration of Performance.
1. A Supplier of Water, subject to the Department's review and written approval, may
be granted Cryptosporidium treatment credit for drinking water treatment processes
based on a demonstration of performance study that meets the following criteria:
a. the demonstration of performance study must follow a Department-approved
protocol and must demonstrate the level of reduction the treatment process will
achieve under the full range of expected operating conditions for the Public Water
System; and
b. the Supplier of Water must demonstrate and report on any monitoring and
treatment performance criteria designated by the Department, where necessary to
verify that the conditions under which the demonstration of performance credit was
approved are maintained during routine operation.
22.20G: continued
2. The Cryptosporidium treatment credit may be greater than or less than the prescribed
treatment credits in 310 CMR 22.20G(12) or (20) through (23) and may be awarded to
treatment processes that do not meet the criteria for the prescribed credits.
3. A Public Water System that receives a Cryptosporidium treatment credit pursuant to
310 CMR 22.20G(21)(c) shall be subject to revocation if the Department determines that
the Public Water System no longer satisfies the criteria set forth in 310 CMR
22.20G(21)(c)1.
4. A Public Water System that receives a Cryptosporidium treatment credit for a
demonstration of performance study shall not receive a Cryptosporidium treatment credit
for any toolbox option specified in 310 CMR 22.20G(20) through (23).
(22) Additional Filtration Toolbox Components.
(a) Bag Filters and Cartridge Filters. A Supplier of Water using Bag Filters or Cartridge
Filters that treat the entire plant flow taken from a Surface Water Source, or Groundwater
under the Direct Influence of Surface Water Source, subject to the Department's review and
written approval, shall receive Cryptosporidium treatment credit, in accordance with the
following:
1. Calculation of Credit. A Cryptosporidium treatment credit of up to 2.0-log for an
individual Bag Filter or Cartridge Filter and up to a 2.5-log for Bag Filters or Cartridge
Filters operated in series shall be granted based on the removal efficiency demonstrated
during challenge testing conducted according to the criteria in 310 CMR
22.20G(22)(a)2.a. through i. A factor of safety equal to 1-log for individual Bag Filters
or Cartridge Filters and 0.5-log for Bag Filters or Cartridge Filters in series shall be
applied to challenge testing results to determine the Cryptosporidium treatment credit.
Suppliers of Water may use results from challenge testing conducted prior to
January 5, 2006, if the prior testing was consistent with the criteria specified in 310 CMR
22.20G(22)(a)2.a. through i.
2. Challenge Testing and Reporting Procedures.
a. challenge testing must be performed on full-scale Bag Filters or Cartridge Filters,
and the associated filter housing or pressure vessel, that are identical in material and
construction to the filters and housings the system will use for removal of
Cryptosporidium. Bag Filters or Cartridge Filters must be challenge tested in the
same configuration that the Public Water System will use, either as individual filters
or as a series configuration of filters;
b. challenge testing must be conducted using Cryptosporidium or a surrogate that
is removed no more efficiently than Cryptosporidium. The microorganism or
surrogate used during challenge testing is referred to as the "challenge particulate".
The concentration of the challenge particulate must be determined using a method
capable of discreetly quantifying the specific microorganism or surrogate used in the
test; gross measurements such as Turbidity may not be used;
c. the maximum feed water concentration that may be used during a challenge test
must be based on the detection limit of the challenge particulate in the filtrate (i.e.,
filtrate detection limit) and must be calculated using the following equation:
Maximum Feed Concentration =1 ×10 × (Filtrate Detection Limit);
d. challenge testing must be conducted at the maximum design flow rate for the
filter as specified by the manufacturer;
e. each filter evaluated must be tested for a duration sufficient to reach 100% of the
terminal pressure drop, which establishes the maximum pressure drop under which
the filter may be used while remaining in compliance with the requirements of
310 CMR 22.20G(22)(a);
22.20G: continued
f. removal efficiency of a filter must be determined from the results of the challenge
test and expressed in terms of log removal values using the following equation:
f
p
LRV = log (C ) - log (C ),
Where:
LRV = log removal value demonstrated during challenge testing;
f
C = the feed concentration measured during the challenge test; and
p
C = the filtrate concentration measured during the challenge test.
In applying this equation, the same units must be used for the feed and filtrate
concentrations. If the challenge particulate is not detected in the filtrate, then the
p
term C must be set equal to the detection limit;
g. each filter tested must be challenged with the challenge particulate during three
periods over the filtration cycle: within two hours of start-up of a new filter; when the
pressure drop is between 45% and 55% of the terminal pressure drop; and at the end
of the cycle after the pressure drop has reached 100% of the terminal pressure drop.
An LRV shall be calculated for each of these challenge periods for each filter tested.
filter
The LRV for the filter (LRV
) shall be assigned the value of the minimum LRV
observed during the three challenge periods for that filter;
h. if fewer than 20 filters are tested, the overall removal efficiency for the filter
filter
product line must be set equal to the lowest LRV
among the filters tested. If 20
or more filters are tested, the overall removal efficiency for the filter product line
filter
must be set equal to the tenth percentile of the set of LRV
values for the various
filters tested. The percentile is defined by (i/(n+1)) where i is the rank of n individual
data points ordered lowest to highest. If necessary, the tenth percentile may be
calculated using linear interpolation; and
i. the results of challenge testing must be reported to the Department.
3. Retesting Requirement. If a previously tested filter is modified in a manner that
could change the removal efficiency of the filter product line, challenge testing to
demonstrate the removal efficiency of the modified filter must be conducted and
submitted to the Department for a determination of whether such change will result in
an adjustment to the overall Cryptosporidium treatment credit previously awarded.
(b) Membrane Filtration. A Supplier of Water using Membrane Filtration, subject to the
Department's review and written approval, shall receive Cryptosporidium treatment credit,
in accordance with the following:
1. Calculation of Credit. The level of Cryptosporidium treatment credit a Public Water
System receives shall be equal to the lower of the values determined in 310 CMR
22.20G(22)(b)1.a. and b.
a. The removal efficiency demonstrated during challenge testing conducted under
the conditions in 310 CMR 22.20G(22)(b)2.a.
b. The maximum removal efficiency that can be verified through direct integrity
testing used with Membrane Filtration under the conditions in 310 CMR
22.20G(22)(b)2.b.
2. Testing and Reporting Procedures.
a. Challenge Testing. The membrane used by the Public Water System must
undergo challenge testing to evaluate removal efficiency and the Supplier of Water
must report the results of challenge testing to the Department. Suppliers of Water
may use data from challenge testing conducted prior to January 5, 2006, if the prior
testing was consistent with the criteria specified in 310 CMR 22.20G(22)(b)2.a.i.
through viii. Challenge testing must be conducted in accordance with the following:
i. challenge testing must be conducted on either a full-scale membrane module,
identical in material and construction to the membrane modules used in the
Public Water System's treatment facility, or a smaller-scale membrane module,
identical in material and similar in construction to the full-scale module.
"Module" as used herein means the smallest component of a membrane unit in
which a specific membrane surface area is housed in a device with a filtrate outlet
structure;
22.20G: continued
ii. challenge testing must be conducted using Cryptosporidium oocysts or a
surrogate that is removed no more efficiently than Cryptosporidium oocysts. The
organism or surrogate used during challenge testing is referred to as the "challenge
particulate". The concentration of the challenge particulate, in both the feed and
filtrate water, must be determined using a method capable of discretely quantifying
the specific challenge particulate used in the test; gross measurements such as
Turbidity may not be used;
iii. the maximum feed water concentration that may be used during a challenge test
must be based on the detection limit of the challenge particulate in the filtrate and
must be determined according to the following equation: Maximum Feed
Concentration = 3.16 x10 x (Filtrate Detection Limit);
iv. challenge testing must be conducted under representative hydraulic conditions
at the maximum design flux and maximum design process recovery specified by the
manufacturer for the membrane module. "Flux" as used in 310 CMR 22.20G means
the throughput of a pressure driven membrane process expressed as flow per unit of
membrane area. "Recovery" as used in 310 CMR 22.20G means the volumetric
percent of feed water that is converted to filtrate over the course of an operating cycle
uninterrupted by events such as chemical cleaning or a solids removal process (i.e.,
backwashing);
v. removal efficiency of a membrane module must be calculated from the challenge
test results and expressed as a log removal value according to the following equation:
f
p
LRV = log (C ) - log (C ),
Where:
LRV = log removal value demonstrated during the challenge test;
f
C = the feed concentration measured during the challenge test; and
p
C = the filtrate concentration measured during the challenge test.
Equivalent units must be used for the feed and filtrate concentrations. If the
p
challenge particulate is not detected in the filtrate, the term C must be set equal to
the detection limit for the purpose of calculating the LRV. An LRV must be
calculated for each membrane module evaluated during the challenge test;
vi. the removal efficiency of a Membrane Filtration process demonstrated during
C-Test
challenge testing must be expressed as a log removal value (LRV
). If fewer than
C-Test
20 modules are tested, then LRV
must be equal to the lowest of the
representative LRVs among the modules tested. If 20 or more modules are tested,
C-Test
then LRV
is equal to the tenth percentile of the representative LRVs among the
modules tested. The percentile is defined by (i/(n+1)) where i is the rank of n
individual data points ordered lowest to highest. If necessary, the tenth percentile
may be calculated using linear interpolation;
vii. the challenge test must establish a quality control release value (QCRV) for a
non-destructive performance test that demonstrates the Cryptosporidium removal
capability of the Membrane Filtration module. This performance test must be applied
to each production membrane module used in the Public Water System's treatment
facility that was not directly challenge tested in order to verify Cryptosporidium
removal capability. Production modules that do not meet the established QCRV are
not eligible for the Cryptosporidium treatment credit demonstrated during the
challenge test; and
viii. if a previously tested membrane is modified in a manner that could change the
removal efficiency of the membrane or the applicability of the non-destructive
performance test and associated QCRV, challenge testing to demonstrate the removal
efficiency of, and determine a new QCRV for, the modified membrane must be
conducted and submitted to the Department for a determination of whether such
change will result in an adjustment to the previously awarded LRV, and an award of
C-Test
a new LRV
.
22.20G: continued
b. Direct Integrity Testing. The membrane used by the Public Water System must
undergo direct integrity testing in a manner that demonstrates a removal efficiency
equal to or greater than the Cryptosporidium treatment credit received pursuant to
310 CMR 22.20G(22)(b)2.a. A "direct integrity test" as used in 310 CMR 22.00G
means a physical test applied to a membrane unit in order to identify and isolate
integrity breaches (i.e., one or more leaks that could result in contamination of the
filtrate). Direct integrity testing must be conducted in accordance with the following:
i. the direct integrity test must be independently applied to each membrane unit
in service. A "membrane unit" as used herein means a group of membrane
modules that share common valving that allows the unit to be isolated from the
rest of the Public Water System for the purpose of integrity testing or other
maintenance;
ii. the direct integrity method must have a resolution of three micrometers or
less, where "resolution" as used in 310 CMR 22.20G means the size of the
smallest integrity breach that contributes to a response from the direct integrity
test;
iii. the direct integrity test must have sensitivity sufficient to verify the
Cryptosporidium treatment credit received pursuant to 310 CMR
22.20G(22)(b)2.a, where "sensitivity" as used in 310 CMR 22.20G means the
maximum log removal value that can be reliably verified by a direct integrity test.
Sensitivity must be determined using the approach in 310 CMR
22.20G(22)(b)2.b.iii.A. or B., as applicable to the type of direct integrity test the
system uses.
A. For direct integrity tests that use an applied pressure or vacuum, the
direct integrity test sensitivity must be calculated according to the following
equation:
DIT
p
breach
LRV
= log (Q /(VCF X Q
))
Where:
DIT
LRV
= the sensitivity of the direct integrity test;
p
Q = total design filtrate flow from the membrane unit;
breach
Q
= flow of water from an integrity breach associated with the smallest
integrity test response that can be reliably measured; and
VCF = volumetric concentration factor. The volumetric concentration factor
is the ratio of the suspended solids concentration on the high pressure side of
the membrane relative to that in the feed water.
B. For direct integrity tests that use a particulate or molecular marker, the
direct integrity test sensitivity shall be calculated according to the following
equation:
DIT
f
p
LRV
= log (C ) - log (C )
Where:
DIT
LRV
= the sensitivity of the direct integrity test;
f
C = the typical feed concentration of the marker used in the test; and
p
C = the filtrate concentration of the marker from an integral membrane unit;
iv. Suppliers of Water must establish a control limit within the sensitivity limits
of the direct integrity test that is indicative of an integral membrane unit capable
of meeting the Cryptosporidium treatment credit awarded by the Department;
v. if the result of a direct integrity test exceeds the control limit established
under 310 CMR 22.20G(22)(b)2.b.iv., the Supplier of Water must remove the
membrane unit from service. The Supplier of Water must conduct a direct
integrity test to verify any repairs, and may return the membrane unit to service
only if the direct integrity test is within the established control limit; and
22.20G: continued
vi. Suppliers of Water must conduct direct integrity testing on each membrane
unit at a frequency of not less than once each day that the membrane unit is in
operation, unless otherwise approved by the Department, based on demonstrated
process reliability, the use of multiple barriers effective for Cryptosporidium, or
reliable process safeguards.
c. Indirect Integrity Monitoring. Each membrane used by the Public Water System
must undergo continuous indirect integrity monitoring according to the criteria
specified in 310 CMR 22.20G(22)(b)2.c.i. through v. "Indirect integrity monitoring"
as used in 310 CMR 22.20G means monitoring some aspect of filtrate water quality
that is indicative of the removal of particulate matter. A Supplier of Water that
implements continuous direct integrity testing of membrane units in accordance with
the criteria in 310 CMR 22.20G(22)(b)2.b.i. through v. is not subject to the
requirements for continuous indirect integrity monitoring. Monthly reports must be
submitted to the Department summarizing all continuous indirect integrity
monitoring results triggering direct integrity testing and the corrective action that was
taken in each case. Indirect integrity monitoring must be conducted in accordance
with the following:
i. unless the Department approves an alternative parameter, continuous indirect
integrity monitoring must include continuous filtrate Turbidity monitoring;
ii. continuous monitoring must be conducted at a frequency of no less than once
every 15 minutes;
iii. continuous monitoring must be separately conducted on each membrane
unit;
iv. if indirect integrity monitoring includes Turbidity and if the filtrate Turbidity
readings are above 0.15 NTU for a period greater than 15 minutes (i.e., two
consecutive 15-minute readings above 0.15 NTU), direct integrity testing must
immediately be performed on the associated membrane unit as specified in
310 CMR 22.20G(22)(b)2.b.i. through v.; and
v. if indirect integrity monitoring includes a Department-approved alternative
parameter and if the alternative parameter exceeds a Department-approved
control limit for a period greater than 15 minutes, direct integrity testing must
immediately be performed on the associated membrane units as specified in
310 CMR 22.20G(22)(b)2.b.i. through v.
(c) Second stage Filtration. A Supplier of Water using second stage Filtration that consists
of sand, dual media, GAC, or other fine grain media following granular media Filtration,
subject to the Department's review and written approval based on an assessment of the design
characteristics of the Filtration process, shall receive 0.5-log Cryptosporidium treatment
credit, in accordance with the following:
1. the first stage of Filtration must be preceded by a Coagulation step;
2. both Filtration stages must treat the entire plant flow taken from a Surface Water
Source or Groundwater under the Direct Influence of Surface Water Source; and
3. a cap, such as GAC, on a single stage of Filtration shall not be eligible for this
Cryptosporidium treatment credit.
(d) Slow Sand Filtration (as Secondary Filter). A Supplier of Water using Slow Sand
Filtration (as secondary filter) that follows a separate stage of Filtration, subject to the
Department's review and written approval based on an assessment of the design
characteristics of the Filtration process, shall receive 2.5-log Cryptosporidium treatment
credit, in accordance with the following:
1. both Filtration stages must treat the entire plant flow taken from a Surface Water
Source or Groundwater Under the Direct Influence of Surface Water Source;
2. no Disinfectant residual may be present in the influent water to the Slow Sand
Filtration process; and
3. Slow Sand Filtration used as a primary Filtration process shall not be eligible for this
Cryptosporidium treatment credit.
(23) Inactivation Toolbox Components.
(a) Inactivation by Chlorine Dioxide and Ozone. A Supplier of Water using chlorine
dioxide or ozone, subject to the Department's review and written approval, shall receive
Cryptosporidium treatment credit, in accordance with the following:
22.20G: continued
1. Calculation of Credit.
a. A Public Water System meeting the chlorine dioxide CT value in 310 CMR