310 CMR 80.42
Requirements for Taking a UST System Temporarily Out-of-service
(1) Owners and Operators shall comply with all requirements in 310 CMR 80.42.
(2) Within 30 days after a UST system is taken temporarily out-of-service, the Owner shall
notify the Department in a format specified by the Department in accordance with 310 CMR
80.23(2)(b).
(3) The Owner or Operator shall not take a UST system temporarily out-of-service for more
than five years.
(a) If a temporarily out-of-service UST system is not put back into service at the end of five
years, the Owner or Operator shall remove or permanently close in-place the UST system in
accordance with 310 CMR 80.43, unless 310 CMR 80.45 applies.
(b) A single-walled steel tank that is temporarily out-of-service on August 7, 2017, shall
comply with the requirements at 310 CMR 80.15.
(4) When a UST system is taken temporarily out-of-service, the Owner or Operator shall
comply only with the following requirements of 310 CMR 80.00 during the entire time period
the UST system is temporarily out-of-service:
(a) Remove all solid and liquid material from the UST system and have the UST system
rendered inert in accordance with 310 CMR 80.47;
The Owner or Operator shall manage the solid and liquid material removed from the UST
system in accordance with all applicable federal, state and local laws and regulations;
(b) Cap, lock and secure all fill lines and fill pipes against tampering;
(c) Keep the vent lines open and operable for the entire period that the UST system is
temporarily out-of-service;
(d) Continue operation and maintenance of corrosion protection in accordance with
310 CMR 80.29, if applicable;
(e) Continue to comply with the third-party inspection requirements in accordance with
310 CMR 80.49;
(f) Comply with the Compliance Certification requirements for temporarily out-of-service
UST systems in accordance with 310 CMR 80.34(3); and
(g) Maintain financial responsibility in accordance with 310 CMR 80.51 through 80.63.
(5) Prior to commencing operation, the Owner or Operator shall have the tank and piping
tightness tested and shall ensure that the UST system components are calibrated and operating
in accordance with the manufacturer's specifications.
(6) Within 30 days after returning the UST system to service, the Owner or Operator shall
notify the Department in a format specified by the Department in accordance with 310 CMR
80.23(2)(c).
(7) Owners or Operators shall demonstrate compliance with the requirements of temporarily
out-of-service by maintaining records/documentation in accordance with 310 CMR 80.36.