522 CMR 2.03
Construction
(1) Heat Recovery Steam Generators (HRSGs). All heat recovery steam generators built after
May 1, 2000, shall be built to the ASME Boiler and Pressure Vessel Code Section I, Rules for
Construction of Power Boilers adopted at the time of installation.
(2) Restrictions, Dual Pressure Controls, Bypass Switches.
(a) Steam Boilers under 522 CMR 2.03 are prohibited from having any device that enables
the Boiler to operate at a pressure less than 10% of its normal operating pressure. Dual
pressure controls or any similar device are prohibited from use on all steam Boilers operating
above 15 PSIG.
(b) Manual devices and switches that allow the bypass of any safety control are prohibited
unless such device or switch is provided with a “dead-man” capability that ensures that the
Operator is present and responsible when the device or switch is in use. No such device or
switch shall have the capability to fail in the closed position.
(3) Remote Monitoring Systems. When remote monitoring systems on Steam Boilers are in
use, they shall monitor, but not be limited to: steam pressure, and water level, and include a
remote shut down switch. All remote monitoring systems must be installed with uninterruptible
system signals and include visible alarms and annunciators.