105 CMR 675.006
Air Sampling Requirements
(A) Operators of indoor skating rinks which utilize combustion resurfacing equipment shall take
regular air samples of both carbon monoxide and nitrogen dioxide within their skating rinks as follows:
(1) an air sample for both carbon monoxide and nitrogen dioxide must be taken at least three
times a week, including at least twice during the week and at least once during weekend
operations;
(2) all air samples must be taken 20 minutes after resurfacing is completed;
(3) all air samples required by 105 CMR 675.000 must be taken no sooner than four hours
before, and no later than one hour before the end of the last scheduled use of the ice in any given
day.
(4) all air samples must be taken either at center ice or the perimeter of the ice surface at the
center ice line at a height of three to six feet above the ice surface;
(B) If an operator of an indoor skating rink utilizes combustion resurfacing equipment less than four
times in any week, the operator shall take an air sample in accordance with the requirements of 105
CMR 675.006(A)(2) and (4) each time it utilizes the combustion resurfacing equipment.
(C) Any individual conducting air sampling must be familiar with the requirements of 105 CMR
675.000 and must be properly trained in the appropriate use of the air monitoring equipment.
(D) The operator shall be responsible for the recording of all air sampling conducted in accordance
with the requirements of 105 CMR 675.000 in the record keeping log, in a manner specified in 105
CMR 675.007. Any air sample ofnitrogendioxide whichresults ina reading below 0.5 ppm shall be
recorded in the record keeping log as “below detection”.